User manual

Installing and Maintaining the Versalar Switch Router 15000
2-20
308684-B Rev 00
Mounting the Versalar 15000 in a Two-Post Rack
To mount the Versalar 15000 in a two-post rack, you need the following
equipment:
A standard 19-inch equipment rack. If the rack does not have threaded rail
holes, you must attach the 8 cagenuts shipped with the Versalar 15000.
Eight cagenut screws and washers (extra screws are shipped with the Versalar
15000).
A Phillips screwdriver.
To install the Versalar 15000 in a two-post rack:
1.
Measure at least 27 in. (68.6 cm) of free vertical space inside the rack and
mark the spot.
2.
Using a Phillips screwdriver, remove the 4 screws securing each of the two
vertical flanges to the Versalar 15000 (Figure 2-9)
.
Note:
You can install three Versalar 15000 platforms in a two-post rack. To
ensure proper ventilation, make sure that there is at least 4 in. (10.1 cm) of
space between them.