Table 2-5 lists the wall receptacle requirements for AC power.
DC Input Electrical Requirements
The installation site must meet the following electrical requirements for DC power
(Table 2-6)
:
Table 2-5. Wall Receptacle Requirements for AC Power
Country Receptacle Voltage
United States and
Canada
National Electrical Manufacturers Association
(NEMA) L6-20R locking receptacle
180-264 V
Any other country Your Versalar distributor attaches the necessary
plug to the power cable and tells you which
receptacle you need.
200-240 V
Table 2-6. Electrical Requirements for DC Model
Nominal Output Voltage
Maximum Output Current Physical
-48/-60 volts direct current
(VDC) nominal
40 A Reinforced insulation from
the main DC power
VRS0120A