Table 23 provides the hardware recommendations for earthquake bracing.
Table 24 lists the maximum sizes of wall studs with a 16-inch spacing.
Table 23
Hardware recommendations
Type of wall Fastener
Vertical spacing
between fasteners
Minimum depth
fasteners must
be embedded in
the wall
Suggested
screw
length
Wood stud #10 Wood Screws 16 in. (400 mm) on center 1 in. (25 mm) 2 in. (50 mm)
Metal stud #14 Sheet Metal
Screws
16 in. (400 mm) on center 1.5 in. (37.5
mm)
Concrete 1/4 in. (6 mm) Hilti
KB-II
24 in. (600 mm) on center 1 1/8 in. (28 mm) 2 in. (50 mm)
Masonry 1/4 in. (6 mm)
Ramset Redhead
Dynabolt Sleeve
Anchor
24 in. (600 mm) on center 2 in. (50 mm)
Table 24
Maximum wall stud sizes — 16 inch spacing
Wall Studs Maximum Height of wall
Wood Studs
2 X 4 (DF #2) 11 ft (3300 mm)
2 X 6 (DF #2) 19 ft (5700 mm)
Metal Studs
2 1/2 X 20 Gauge 9 ft (2700 mm)
2 1/2 X 16 Gauge 10 ft (3000 mm)
2 1/2 X 14 Gauge 11 ft (3300 mm)
3 5/8 X 20 Gauge 12 ft (3600 mm)
3 5/8 X 18 Gauge 13 ft (3900 mm)
3 5/8 X 16 Gauge 14 ft (4200 mm)
3 5/8 X 14 Gauge 16 ft (4800 mm)
4 X 20 Gauge 14 ft (4200 mm)
4 X 18 Gauge 15 ft (4500 mm)