GS Series Gas Steam Humidifier Installation, User & Maintenance Guide IMPORTANT: Read and save this guide for future reference. This guide to be left with equipment owner.
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS: Do not try to light any appliance. Do not touch any electrical switch; do not use any telephone in your building. Immediately call your gas supplier from a neighbor’s telephone. Follow the gas supplier’s instructions. If you can not reach your gas supplier, call the fire department. UNIT OPERATING RANGES: Max. Ambient Temperature 104ºF (40ºC). Min.
Table Of Contents GENERAL 1 - WARNING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - DELIVERY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - RECEIVING & UNPACKING EQUIPMENT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - GENERAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - MODEL DESIGNATION . . . . . . . . . . . . . . . . . . . . . .
PRINCIPLE OF OPERATION 22 - COMBUSTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 - WATER MANAGEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 - START UP PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 - FILLING THE SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 - TESTING THE IGNITION SAFETY SHUT-OFF. . . . . . . . . . . . . . .
RECEIVING & UNPACKING EQUIPMENT GENERAL This installation guide has been designed to provide assistance when installing, mounting, and commissioning a GS Series humidifier. Actual on site application may vary. Consult Technical Services or your local NORTEC representative. · Check packing slip to ensure ALL material has been delivered. · All material shortages are to be reported to NORTEC within 48 hours from receipt of goods. NORTEC assumes no responsibility for any material shortages beyond this period.
MODEL SPECIFICATION MODEL GS 100 SPECIFICATIONS FUEL BLOWER SPEED INPUT (BTUH)* STEAM CAPACITY (LBS/HR) MANIFOLD PRESS. IN W.C. NATURAL GAS MAX 140,000 105 -0.05 MIN 45,000 25 -0.05 PROPANE MAX 140,000 105 -0.35 MIN 50,000 25 -0.35 MODEL GS 200 SPECIFICATIONS FUEL BLOWER SPEED INPUT (BTUH)* STEAM CAPACITY (LBS/HR) MANIFOLD PRESS. IN W.C. NATURAL GAS MAX 280,000 210 -0.05 MIN 45,000 25 -0.05 MAX 280,000 210 -0.35 MIN 50,000 25 -0.
HIGH ALTITUDE - A derate in input exists for installations at higher altitudes. For Canadian models, an automatic 10% derate applies to installations from 2000-4500 feet. For U.S. Models, refer to the chart below for high altitude derate information. FOR U.S.
Figure #2 Clearance Requirements Front Clearance Side Clearance Minimum 4" (10.2 cm) to vent pipe Minimum 36" (91.5 cm) Left 36" (91.5 cm) Front 30" (76.2 cm) Required only for GSTC/GSP 500/600 Right 30" (76.2 cm) Optional Stand · Ambient temperature location for humidifier: 41ºF - 104ºF (5ºC - 40ºC). INDOOR INSTALLATION The installation must conform with local building codes or, in the absence of local codes, with the ANSI Z223.1, National Fuel Gas Code, and/or CAN/CGA B149 Installation Codes.
· DO NOT mount humidifiers in an area where freezing may occur. The gas inlet pipe size to the appliance is: ½” NPT for GS 100 ¾” NPT for GS 200 1” NPT for GS 300 / 400 1 ¼” NPT for GS 500 / 600 · If humidifiers are mounted on a roof, a properly ventilated, temperature controlled, (above freezing), weatherproof enclosure must be used. Provide an adequate size gas supply line. · DO NOT mount humidifiers on vibrating surface. Consult factory.
recommended that the supply air line is insulated and an in line heat is added. Consult factory. upstream of the gas supply connection to the appliance. Attach the air supply line to the manifold using a hose clamp or hose coupling if required. See Figure #4. COMBUSTION AIR REQUIREMENTS Provide for adequate combustion and ventilation air in accordance with Sections 8.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, or Sections 7.2, 7.3, 7.
· In applying the codes, reference should be given to the venting manufactures instructions, the serving gas supplier regulations, and the specific instructions provided in this manual. Location of air intake and flue gas terminal must comply with all local and national regulations. EXHAUST VENTING The GSTC and GSP are classed category I and III fan assisted gas appliances. This allows two methods of venting.
Figure #7 Vertical Venting Application Using B or BH Venting UL Listed Cap Required Flashing B or BH type vent using double wall vent with double wall connectors is required. Reference local and/or national codes before installation of the vent. 4" minimum air space required Horizontal run 1/4"rise per ft Exhaust venting outlet Steam Outlet Condensate tee required Trap 2 FT Min 3” Min. Condensate tee and trap must be installed. Take the condensate to a floor drain or a condensate pump.
Figure # 9 Co-venting Application Using B Vent Only UL Listed Cap Required B type double wall vent with double wall connectors is required for category I, serving two or more gas appliances. Condensate tee and trap must be installed. Take the condensate to a floor drain or a condensate pump. Exhaust venting outlet Condensate Tee Steam Outlet Trap Category I gas appliance uses B type venting. Follow local and/or national codes for venting installation. Note: These are guidelines only.
· Vent connectors shall not be connected into any portion of a mechanical draft system operating under positive pressure. · Vent pipe must be secured with hangers or pipe straps · All horizontal runs must be adequately supported with hangers or straps to prevent sagging. · The GS series humidifiers have a fan-assisted combustion which operates with a non-positive vent static pressure when installed with the appropriate vent diameter. · Use only double wall (aluminum inner wall) B vent.
· This appliance should not be connected to a chimney flue servicing a separate appliance designed to burn solid fuel. Never connect this humidifier to a chimney servicing a fireplace. WARNING: Provide a screen or barrier to prevent personal injury in areas where inadvertent personnel contact with vent pipe can occur. · A minimum equivalent vent length of 7 feet must be connected to the humidifier. Vent lengths must not exceed 100’ (30 m). Each 90° elbow is equivalent to 10’ and each 45° elbow equals 5'.
Field wiring from humidistat to humidifier and between devices should be shielded 18 AWG or heavier and kept as short as possible. The vent terminal must be installed in the same atmospheric pressure zone as the combustion air inlet of the humidifier. If this is not possible (as in cases of positive or negative room pressures) the humidifier should be installed with the direct vent option. Controls are available from NORTEC as accessories and can be ordered with the humidifier.
VOLTAGE PRIMARY 208-240V 1 phase line voltage wiring to unit (BY OTHERS) (ACTUAL) Ground Wire Ground Leg Ground 600V/3ph L1 Step down Transformer 600V/208V by others L2 L3 Dedicated Circuit Breaker Or Disconnect Note: - 600V/3 Phase Supply. - 600V/1ph between any two hot leg. - 347V/1ph between hot and neutral.
GS SERIES EXTERNAL CONTROLS WIRING CONNECTIONS LOW VOLTAGE TERMINAL STRIP NOTE: This is a generic wiring diagram only. For specific wiring instructions, it is necessary to refer to the wiring diagram which is supplied with each unit. EXTERNAL INTERNAL N.C. COM N.O. Humidifier “FAULT” Humidifier “SERVICE” N.O. COM Humidifier “ACTIVE” N.O. COM N.O.
· It is recommended to have a faucet installed close to the humidifier to allow quick filling of the system on initial start up. This can also be very useful for mandatory cleaning of the unit. CONTROL INSTALLATION · Mount any wall humidistat (control or high limit) over standard electrical box at height similar to typical thermostat. Any wall humidistat should be in location representative of overall space being humidified and not in path of blower pack or air supply grille.
· The drain line should not end in a sink used frequently by personnel, or where plumbing codes prohibit it. Route to a floor drain or equivalent for safety reasons. Internal drain water tempering will ensure a maximum of 140ºF (60ºC) exiting water temperature. Figure #12 Steam Line Connection Steam Line · Never install PVC piping as a drain line material. Always use material suitable for with-standing 140ºF (60ºC). Snap on Insulation · Keep drain lines as short as possible.
Figure # 13 GSTC Outdoor Typical Installation Rooftop BH Vent (By Nortec) AHU Insulated Steam Line (By others) Electrical Disconnect (By others) Roof Curb (By others) Gas Line with Manual Shut-off (By others) Water Supply Drain Lines Funnel With Air Gap Manual Shut-off Figure # 14 GS Outdoor Typical Installation Rooftop BH Vent (By Nortec) Insulated Steam Line (By others) Electrical Disconnect (By others) Roof Curb (By others) Gas Line with Manual Shut-off - 17 -
Figure # 15 GSTC Outdoor Clearance Minim um Re quire d Cle a ra nce s GSTC GSTC GSTC GSTC GSTC GSTC Mode l Outdoor Outdoor Outdoor Outdoor Outdoor Outdoor 100 200 300 400 500 600 Front 30" (76cm) 30" (76cm) 30" (76cm) 30" (76cm) 30" (76cm) 30" (76cm) Le ft 0 0 30" (76cm) 30" (76cm) 30" (76cm) 30" (76cm) 40" 40" 40" 40" 40" 40" Right (101.6 (101.6 (101.6 (101.6 (101.6 (101.6 cm) cm) cm) cm) cm) cm) 6" 6" 6" 6" 6" 6" Ba ck (15.25 cm) (15.25 cm) (15.25 cm) (15.25 cm) (15.25 cm) (15.
· The integral base of the GS Outdoor model is designed to mount on a curb. The curb must be built to structurally support the entire weight of the humidifier when in operation. Required curb dimensions are given in Figure #16 . · Gas lines are to be routed to the outside connection on the right side near the back of the unit. The installation of a sediment trap and a certified manual shut-off valve are required outside of the unit.
Figure #18 GasPiping · Each vent length and the rain cap have a built-in mechanical locking band and gasket. Simply push together each component to the stop bead, which provides an air & water-tight seal. Then tighten the integrated locking band on each component to complete the installation of the exhaust venting. · The rain cap must extend at least 2 feet above any ridge within 10 feet of the unit. The exhaust venting can be extended using additional vent lengths purchased from Nortec.
Figure #22 Drain Connection FILL WATER SUPPLY LINE · Each unit is supplied with a ½” NPT male connection to the fill valve. Refer to Figure #21 for connection details. A minimum fill rate of 10 l/min (2.6 gal/min) is required for all unit sizes. Allowable pressure range is 30-80 psig. · Always install a manual shut off within the building to allow isolation of the water to the unit. A union must be installed on the fill line prior to the fill valve to allow for servicing.
STEAM LINES PRINCIPLES OF OPERATION · The steam outlet connection is located at the back of the GS Outdoor unit. Steam hose(s) and clamps are supplied with the unit and are intended to provide a flexible coupling outside of the unit to the building steam lines. See Figure #23. Combustion The combustion system is based on a fully modulating forced draft combustion air blower(s), a negative pressure regulated gas valve, and a 100% premix burner.
Qualified personnel must correct any deficiencies with the installation before commissioning takes place. On initial start-up, the solenoid operated fill valve fills the tank. The water level reaches the backup float first and then the main float. If the backup and main floats do not read the same water level during the operation of the unit, the unit will shut down on a fault. The unit will continue to fill the unit to the top green position.
· At the completion of the float test, the humidifier will begin the combustion sequence by energizing the combustion blowers · At the completion of the float test, the humidifier will begin the combustion sequence and each burner will ignite in sequence · All blowers will run at full output for 30 seconds to pre-purge the combustion chamber.
GS INSPECTION CHECK LIST HUMIDIFIER MOUNTING £ Verify proper clearances around the unit £ Humidifier mounted level £ Humidifier properly secured to stand and stand bolted to floor £ All service doors accessible £ Roof curb sized correctly (Outdoor Model Only) GAS PIPING £ Correct gas line size installed £ Certified manual shut off valve and union installed £ Sediment trap installed £ Gas piping leak tested £ Air purged from lines £ Proper gas supply pressure £ Regulator dedicated for each gas unit EXHAUST G
SUPPLY WATER LINE £ Nortec supplied adapter installed on fill valve (½”NPT) £ Manual shut off valve and union installed £ Verified pressure (30 – 80 psig) £ Water source of 10 l/min (2.6 gpm) £ Leak tested £ ½” dia. At max 4ft of the unit DRAIN LINES £ Air gap located within 3ft of the unit £ Minimum drain line size of 1” in dia.
Figure #25 Site Water Test Kit P/N 1507214 · Close the shut-off valve in the water supply line · Isolate the humidifier from the electrical power supply at the main disconnect switch SCALE MANAGEMENT The gas humidifier will periodically “blowdown” water from the tank to reduce the concentration of total dissolved solids that accumulate during long term operation. Gas Humidifiers are shipped factory set with a blowdown of 25%.
· Conductivity: Measured in micromhos. Follow the directions for the conductivity pen found inside the box. Multiply the digital reading by 1.5. The recommended operating range for conductivity is 0 - 1500 micromhos. Consult the factory is you measure outside these parameters. Technology GasFired Water Type A history of all faults is stored in memory of the software and can be viewed through the service level on the display. Refer to the keypad display menu structure at the end of the manual.
- 29 X X X X Gas Venting X H/L Stack Sensor X Drain Lines X X X Fill Lines X Direct Vent X Float Chamber X X X X X X X X X Drain Lines X X Gas Burner Tank X END OF SEASON Flame Sensor MID X 30 DAYS after initial start-up Hot Surface Ignitor PARTS - Visual check that sensor is intact, wired and attached to the exhaust. - Inspect for leaks. Ensure intake terminal is clear. - Inspect for leaks.
· Ensure that power is switched on again during periods of demand. exchanger walls. DO NOT use a metal scraper that will scratch the stainless steel surfaces of the tank. Once all large pieces of scale have been removed, vacuum the tank out with a shop vacuum, fill part way with water, and flush remaining sediment from the tank through the drain. · The GSTC model of the Gas Steam humidifier includes a pre-cleaning sequence feature.
NOTE: Proper polarity of supply voltage to the unit is necessary for flame sensing to occur. Oxidation on flame sensing rod can reduce measured current. The oxidation can be cleaned from the sensing rod using steel wool or an emery cloth. The switch board must be replaced into the same position as before cleaning and the tie -wrap must be used to hold the float chamber in position. SERVICING THE UNIT Igniter Check Caution: Disconnect power before servicing this appliance.
6. Once the pressure has been adjusted, replace the locking cap. gasket when replacing the flame sensor and igniter. 7. Replace the screw in the “out” pressure port and tighten firmly. CAUTION: The silicon carbide igniter is breakable. Handle with great care to avoid damage. COMPONENT REPLACEMENT Burner Removal and Installation CONSULT FACTORY PRIOR TO THE REPLACEMENT OF ANY COMPONENT. 1. Shut off electrical power and gas supply to the humidifier.
any gaskets that may be damaged. When mounting the gas valve/air inlet assembly to the combustion blower, ensure that the cork gasket is properly oriented or gas flow through the valve will be impeded. with a new burner. Inspect and replace any gaskets that may be damaged. Tighten the 4 brass nuts of burner mounting plate to a torque of 95 in-lb. 8. Leak test the gas train before re-commissioning the humidifier. 9. Leak test the gas train before re-commissioning the humidifier.
5. Remove screws (2) holding the switch. Figure #30 Gas Valve Replacement 6. Reverse above procedure to re-install. Float Chamber Replacement 1. Drain the contents of the tank and then shut off electrical power and water supply to the humidifier. 2. Remove the left front service access door. 3. Remove the cable connection to the float board. 4. Remove the hose clamps on the float chamber and remove all hoses (note the correct hose assignment). 5.
Ignition Module Replacement Figure #34 Transformer Assembly 1. Shut off electrical power to the humidifier. 2. Remove the front electrical access door. 3. Disconnect all wiring connections to the ignition module, labeling as required. 4. Remove the 2 screws securing the ignition module and remove. 5. Reverse the above sequence to install the new module. Figure #33 Ignition Module Assembly Fill Valve Replacement 1. Shut off electrical power and water supply to the humidifier. 2.
Drain Pump Replacement 1. Drain the unit completely. If the pump is broken use the auxiliary drain out port. 2. Shut off electrical power to the appliance. 3. Remove front and right doors. 4. Remove wiring connections to the pump. 5. Remove hoses attached to the pump. 6. Reverse above procedure to re-install. NOTE: To avoid water spillage (some water will be left on the tank bottom after manual draining) use shop vac to remove left over water.
Removal of Heat Exchanger Figure #38 Heat Exchange Assembly 1. Take the humidifier out of operation. 2. Disconnect the gas supply pipe from the connection on the humidifier and close off the pipe. 3. Unlock and remove the right side panel(s). 4. On Direct Vent units only: Remove hoses from air intake manifold and air inlet elbows. 5. Dismount flue gas pipe at the flue gas outlet connection. 6. On Direct Vent units only: Dismount air supply pipe at the air supply connection. 7.
- 38 -
3 DAY DRAIN 3 DAY DRAIN FUNCTION SW3/7 Function Disabled OFF Function Enabled (Factory set) ON KEEP WARM 3 DAY DRAIN FUNCTION SW5/7 Function Enabled ON Function Disabled (Factory set) - 3 day drain OFF MAINTENANCE (GSP) MAINTENANCE INTERVAL (GSP) SW3/8 500 hour (Factory set) OFF 1000 hour ON ANALOG CHANNEL 1 Input Range SW1/1 SW4/1 SW 4/2 0-10V input OFF OFF OFF 0-5V input OFF ON OFF 2-10V input OFF OFF ON 1-5V input OFF ON ON 0-20mA input ON OFF OFF 0-10mA input O
INPUT CHANNEL DUAL CHANNEL FUNCTION SW4/5 One Channel Input OFF Dual Channel Inputs ON TIME PROPORTIONING TIME PROPORTIONING SW4/7 Disabled (Factory set) OFF Enabled ON BLOWDOWN (GSP) BLOWDOWN SW5/1 SW 5/2 SW5/3 5% ON OFF OFF 10% OFF ON OFF 15% ON ON OFF 20% OFF OFF ON 25% (Factory set) ON OFF ON 30% OFF ON ON 35% ON ON ON MAINTENANCE SHUTDOWN MAINTENANCE SHUTDOWN FUNCTION SW5/4 Unit will shutdown 72 hours after service time expired, by generating an error.
NORTEC TC CONTROLLER Menu Structure INTRODUCTORY SCREEN MAIN MENU NORTEC GSTC-400 VERSION X.XX MENU SYSTEM LOCKOUT MENU SYSTEM STATUS SERVICE LEVEL USER SETTINGS 09.05.02 9:30 USE THE UP/DOWN ARROWS TO MOVE THE POINTER TO SELECT A MENU ITEM. TO OPEN THE SELECTION, PRESS THE ENTER BUTTON.
SYSTEM STATUS 1 of 2 MAIN MENU SYSTEM STATUS STATUS: USER SETTINGS 1 LOCKOUT MENU DEMAND CHANNEL 1 0% ENTER DEMAND CHANNEL 2 0% 2 CAPACITY LIMIT 0% 1 BURNERS ACTIVE X/X OUTPUT/BURNER XXXLB 2 3 TOTAL OUTPUT 2. ONLY VIEWED IF UNIT IS CONFIGURED FOR DUAL CHANNEL. 1. DISPLAY WILL SHOW NUMBER OF BURNERS AND DISPLAYS THE NUMBER OF ACTIVE BURNERS. SYSTEM DEMAND XXX% MENU 1. DISPLAY TOGGLES BETWEEN LOCKOUT, ACTIVE, AND STANDBY, DEPENDING ON SYSTEM DEMAND XXXLB 2.
SYSTEM STATUS 2 of 2 SYSTEM STATUS 1 MAIN MENU 1. DISPLAYS THE USER SELECTABLE MAINTENANCE INTERVAL SYSTEM STATUS SERVICE LEVEL MENU USER SETTINGS ENTER MENU SERVICE INTERVAL 1 XXX HOURS REMAINING XXX HOURS 2 START DATE: MM:DD:YY 3 SECURITY LOOP [0/1] 1 SAFETY SENSORS [0/1] 2 TANK SENSORS [0/1] 3 2. DISPLAYS THE TIME LEFT BEFORE MAINTENANCE IS DUE 3. DISPLAYS THE START DATE OF THE CURRENT SERVICE INTERVAL 1. DISPLAYS STATUS OF THE SECURITY LOOP (O = OPEN I = CLOSED) 2.
SERVICE LEVEL 1 of 2 MAIN MENU SYSTEM STATUS SERVICE LEVEL MENU USER SETTINGS ENTER SERVICE INTERVAL SERVICE HISTORY FAULT HISTORY TANK DRAIN TANK PRE-CLEAN BURNERS SHORT CYCLE DELAY SERVICE INTERVAL XXX HOURS 1 SERVICE INTERVAL XXX HOURS SERVICE (HR) CHANGE VALUE XXX CLEAR REMAINDER? 1. VERTICAL ARROW INDICATES ADDITIONAL SERVICE INTERVAL XXX HOURS SELECTIONS AVAILABLE BY SCROLLING. 2. USE UP DOWN ARROWS TO CHANGE HOURS 3 3.
SERVICE LEVEL 2 of 2 SERVICE LEVEL 1 MAIN MENU SYSTEM STATUS SERVICE LEVEL MENU USER SETTINGS ENTER MENU MENU SERVICE INTERVAL SERVICE HISTORY FAULT HISTORY TANK DRAIN TANK PRE-CLEAN BURNERS SHORT CYCLE DELAY SERVICE INTERVAL SERVICE HISTORY FAULT HISTORY TANK DRAIN TANK PRE-CLEAN BURNERS SHORT CYCLE DELAY SERVICE INTERVAL SERVICE HISTORY FAULT HISTORY TANK DRAIN TANK PRE-CLEAN BURNERS SHORT CYCLE DELAY THIS WILL DRAIN CONTENTS OF TANK THIS WILL DRAIN CONTENTS OF TANK 1 CONTINUE? 1 1.
USER SETTINGS 1 of 3 CHANGE TIME 0335 MAIN MENU SYSTEM STATUS SERVICE LEVEL MENU USER SETTINGS ENTER DATE/TIME/UNITS LANGUAGE CONTROLS WATER MANAGEMENT CONTROL TYPE CAPACITY LIMIT CALIBRATE 1 TIME HH:MM DATE MM.DD.YY UNITS: LB/HR XX:XX CHANGE DATE 0335 MM.DD.YY SELECT UNITS 1. VERTICAL ARROW INDICATES ADDITIONAL SELECTIONS AVAILABLE BY SCROLLING.
USER SETTINGS 2 of 3 FTBD HOURS 0335 CHANGE HOURS? XXX FTBD HOUR 0335 CHANGE HOUR? XX BLOWDOWN RATE USER SETTINGS PAGE 1 0335 CHANGE VALUE XX% STEAM OUTPUT MAIN MENU SYSTEM STATUS SERVICE LEVEL MENU USER SETTINGS ENTER DATE/TIME/UNITS LANGUAGE CONTROLS WATER MANAGEMENT CONTROL TYPE CAPACITY LIMIT CALIBRATE USER SETTINGS 3 1 FTBD HOURS XXX FTBD HOUR XX BLOWDOWN RATE XX% FLOAT CHECK HH:MM FILL CORRCTN XX% DRAIN CORRCTN XX% DRAIN COOL: SMART 1.
USER SETTINGS 3 of 3 USER SETTINGS 2 MAIN MENU SYSTEM STATUS SERVICE LEVEL MENU USER SETTINGS ENTER DATE/TIME/UNITS LANGUAGE CONTROLS WATER MANAGEMENT CONTROL TYPE CAPACITY LIMIT CALIBRATE CONTROL TYPE CONTROL TYPE CONTROL INPUT 1 0335 TRANSDUCER INPUT CONTROL INPUT TRANSDUCER INPUT PRESS ENTER TO SELECT CONTROL TYPE 1. VERTICAL ARROW INDICATES ADDITIONAL SELECTIONS AVAILABLE BY SCROLLING.
NORTEC TC CONTROLLER User Settings: (password protected) INTRODUCTORY SCREEN This section allows the user to set parameters specific to their requirements. For further details see specific section below. NORTEC GSTC-400 VERSION X.XX Diagnostics: (safety loop protected) SYSTEM LOCKOUT Allows the user to activate and monitor various system operations. 06.07.
Output/Burner: SYSTEM STATUS This field will display the actual output of steam generated by each burner (kg/hr or lbs/hr). SCREEN 1: Total output: STATUS: LOCKOUT DEMAND CHANNEL 1 0% DEMAND CHANNEL 2 0% CAPACITY LIMIT 0% This field will display the total system steam output (kg/hr or lbs/hr). SCREEN 3: Status: WATER LEVEL: X FILL VALVE ON DRAIN VALVE OFF DRAIN COOLING: SMART Displays the present status of the system.
closed the display will indicate “1”. Closed indicates that the tank temperature is above 160ºF (70ºC). SCREEN 4: This input is used for the “keep warm” feature and for activating the fill valve during blowdown cycles. SERVICE INTERVAL XXX HOURS REMAINING XXX HOURS START DATE: MM:DD:YY SCREEN 6: 3 DAY DRAIN 1 KEEP WARM 0 BLOWDOWN RATE XX% Service interval: This field displays the user (or factory default) setting for the humidifiers service reminder in steam hours.
SERVICE LEVEL SERVICE INTERVAL SERVICE HISTORY FAULT HISTORY TANK DRAIN TANK PRE-CLEAN BURNERS SHORT CYCLE DELAY The service level area is where service related tasks are performed. Below is a description of each field and what can be performed in them. When a parameter requires a change, press the two arrow keys and enter the password (0335). As long as you remain in this section, you will not need to enter the password more than once.
Y = total number of recorded services (up to 10 maximum). STEAM HOURS XXX (DATE/TIME) This field displays the steam hours and the date and time when the specific service (X) was performed. SERVICE INTERVAL SERVICE HISTORY FAULT HISTORY TANK DRAIN TANK PRE-CLEAN BURNERS SHORT CYCLE DELAY FAULT HISTORY X/Y (TYPE OF FAULT) (DATE/TIME) Fault history In this area the customer can view the history of recorded faults for the humidifier. FAULT HISTORY X/Y The fault history stores the last 54 system faults.
Tank Pre-Clean The tank pre-clean feature when activated will activate the drain valve for a fixed period of time (depending on unit size). The fill valve will then activate, filling the tank partially with cold water. At the completion of the fill cycle the tank will once again drain. This will help to flush out any accumulated minerals as well as cool the tank for the service personnel. To pre-clean the tank press enter when CONTINUE is selected.
User Settings DATE/TIME/UNITS LANGUAGE CONTROLS WATER MANAGEMENT CONTROL TYPE CAPACITY LIMIT CALIBRATE When a parameter requires a change, press the two arrow keys and enter the password (0335). As long as you remain in this section, you will not need to enter the password more than once. Date / Time Units This field is used for modifying the Date, time and the units of measurement. The date and time are important parameters when features such as full tank blowdown are enabled.
Language Controls DATE/TIME/UNITS LANGUAGE CONTROLS WATER MANAGEMENT CONTROL TYPE CAPACITY LIMIT CALIBRATE SELECT LANGUAGE ENGLISH FRENCH GERMAN SELECT LANGUAGE ENGLISH FRENCH GERMAN This field allows the user to select the menu language of choice (English, French, German) Here the user can select the language of choice for the menu displays. To set the language, highlight the selection then enter the user code (0335). Press enter. Use the UP/DOWN arrows to select the choice (English, French, German).
FTBD Hour Works in conjunction with FTBD hours. DATE/TIME/UNITS LANGUAGE CONTROLS WATER MANAGEMENT CONTROL TYPE CAPACITY LIMIT CALIBRATE FTBD HOURS FTBD HOUR BLOWDOWN RATE FLOAT CHECK FILL CORRCTN DRAIN CORRCTN DRAIN COOL: XXX XX XX% HH:MM XX% XX% ON 0335 BLOWDOWN RATE CHANGE VALUE XX% STEAM OUTPUT Here the user sets the time of day (24 hour format) when they want the FTBD to execute. The time can be set to trigger the cycle during off hours, when the humidity requirements are minimal.
Fill CORRCTN (correction) Used for adjusting the fill rate. Adjustments to be made under factory direction only. Drain CORRCTN (correction) Used for adjusting the drain rate. Adjustments to be made under factory direction only. Drain Cool The customer can select the type of drain water tempering they require (depending on local plumbing codes) The customer can select ON, OFF, or SMART. ON – whenever the drain valve is activated through software, the fill valve will automatically activate.
Transducer Input This section is used to configure the controller for transducer signals In this section you can adjust the proportional, integral and derivative constants. There is also a PID learn algorithm which will tune the various PID constants for optimal performance. Capacity Limit In this section the customer can adjust the maximum output of the humidifier between 25-100%. To adjust the maximum capacity, highlight the selection then enter the user code (0335). Press enter.
FAULT LIST GSTC fault displayed GSP fault code displayed Description of fault FAULT NO BURNERS AVAILIBLE NBF Once the GS controller detects an ignition module fail, it will index to the next available ignition module.
FAULT LIST FAULT GAS RE-IGNITION BURNER X GIF-X Following an ignition module fault if the modules gas valve activates this fault will be generated. FAULT DRAIN NOT WORKING DRAIN IS BLOCKED DBF There are many time windows in the GS software.
WARNING LIST GSTC Warning displayed GSP warning displayed Description of warning: WARNING IGNITION MODULE X FAIL IMW-X Once the controller activates an ignition module, it will allow 4 minutes for the gas valve to activate. After the trial period, if the gas valve has not activated, a fault will be generated. The module will be locked out and the next burner will be indexed.
- 63 -
GS Series Internal Components Spare Parts Number Description Part # GS 100 GS 200 GS 300 GS 400 GS 500 GS 600 101 Cover Plate, Clean-Out Port 2523457 1 1 2 2 3 3 102 Gasket, Tank Cover Plate 2524361 1 1 2 2 3 3 103 Secondary Safety Switch 1504832 1 1 1 1 1 1 104 Fill Box 2526152 1 1 1 1 1 1 105 Vacuum Break Valve ½” npt 1505959 1 1 1 1 1 1 106 P-Trap 2526521 107 Dual Fill Valve 10.0 l/min & 0.
GS Series Internal Components Spare Parts - continued Number Description Part # GS 100 GS 200 GS 300 GS 400 GS 500 GS 600 1506892 1 2 3 4 5 6 110-120V Models 2528418 1 2 3 4 5 6 208-240V Models 1507695 1 2 3 4 5 6 1507694 1 2 3 4 5 6 110-120V Models 2528420 1 2 3 4 5 6 208-240V Models 1507712 1 2 3 4 5 6 110-120V Models 2524360 1 2 3 4 5 6 208-240V Models 1502289 1 2 3 4 5 6 1504175 1 2 3 4 5 6 Natural Gas 1507713 1 2 3 4 5
- 66 -
GS Series Indoor Cabinetry Spare Parts Number 201 Description Part # GS 100 Mini 2524439 1 Single 2524440 Double 2524441 Triple 2524458 GS 200 GS 300 GS 400 1 1 GS 500 GS 600 1 1 Service Door Assembly 1 202 Fron t Door Assembly 2528421 1 1 1 1 1 1 203 Recessed Handle 2523444 1 1 1 1 2 2 204 Transformer 24/16V 15VA 50/60 hz 1505760 1 1 1 1 1 1 205 Logic Control Board 1505762 1 1 1 1 1 1 206 I/O Board 1504760 1 1 1 1 1 1 207 Primary Transfo
- 68 - 14 13 15 16 12 3 20 19 21 22 18 9 17 8 5 1 6 42 4 7 41 10 44 11 24 26 43 27 36 29 28 40 35 30 GS Series Outdoor Cabinetry Exploded View 2 25 23 37 31 38 33 32 39 34
GS Outdoor Spare Parts List 1 2 3a 3b 3c 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Description Transformer 24/16V 15VA Transformer 208-24Vac 250VA Fuse 6.
25 Fan Hood 26 Cover Plate Top Panel 27 Gasket, Steamline 28 29 30 31 32 33 34 35 36 37 38 39 100 200/300 400/500/600 Cover Plate Steam Line 100 200/300 400/500/600 Step-up transformer (120/240V option) Mounting bracket, step-up transformer Mid Cross Member Mini Single Double Triple Gas Line Bracket Rear Frame Element Rear Panel Cross Member Mini Single Double Triple Mounting bracket, float chamber Front Frame Right Panel Mini Single Double Triple Access Door, Side 40 Base Assembly Mini Single Doubl
-71 - 7 36 4 2 A 1 6 DETAIL B THE MIDDLE SECTION IS USED ONLY FOR GS300/400 AND GS500/600 (SHOWN THE STAND FOR GS300/400) B 2 5 1. UNPACK STAND AND CHECK THAT ALL PIECES ARE PRESENT AND UNDAMAGED. 2. ASSEMBLE STAND TO CONFIGURATION SHOWN ON SHEET 1. HAND TIGHTEN ALL BOLTS ONLY. 3. HOIST HUMIDIFIER UP ABOVE THE FLOOR A MINIMUM OF 32 IN (812.8 MM). 4. POSITION STAND BELLOW THE LEGS OF THE HUMIDIFIER. ALIGN HUMIDIFIER AND STAND SO THAT HOLES IN THE HUMIDIFIER BASE ALIGN WITH HOLES IN STAND. 5.
GS Quick Reference Item GS 100 GS 200 GS 300 GS 400 GS 500 GS 600 Gas Pressure Natural Gas min "wc/mbar 5/14 Natural Gas max "wc/mbar 9/22 Propane min 10/23 Propane max 14/34 Min free air opening in/cm 13/33 23/58 35/89 47/119 59/150 71/180 140,000 280,000 420,000 560,000 700,000 840,000 Input BTU's Max Min GSTC 45,000 Direct vent min 60,000 Gas Piping Size in/cm 1/2/1.3 3/4/1.9 1/2.5 1/2.5 1.25/3.2 1.25/3.2 "BH" Vent X X X X X X "B" Vent X X X X X X 3/7.
LIMITED WARRANTY Walter Meier Inc. and/or Walter Meier Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years from date of shipment, that THE COMPANY's manufactured and assembled products, not otherwise expressly warranted, are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations.
826 Proctor Avenue, Ogdensburg, New York 13669 Walter Meier (Climate Canada) Ltd. 2740 Fenton Road, Ottawa, Ontario K1T3T7 Tel: 866 NORTEC 1 Fax: 613 822 7964 northamerica.climate@waltermeier.com www.humidity.com PRINTED IN CANADA Walter Meier (Climate USA) Inc.