s Manual

22
Technical data
Voltage range
SAFE 1/1.1 / SAFE 2/2.1/2.2 / SAFE S.6 / SAFE 4/4.1 / SAFE M 0,9 to 1,1 UB
RS-NAGV / RS-NAGT/T.1 / SAFE L/L.1 / SAFE L.2 / SAFE Z / SAFE IRZ.2
RS-NAGU.12 / RS-NAGU.1 / RS-NAGU.2f
RS-NAGMP/P.1 / RS-NAGA/AO 0,85 to 1,1 UB
SAFE IL1 / SAFE 5/5.1 / RS-NAGL/L.1 / SAFE ILL / SAFE Z.2 / RS-NAGZ / SAFE ILZ
SAFE X4/4.1 / RS-NAGX5 / SAFE IL2 / FI1
SAFE C1, CL, CM, CZ, SAFE TU/ TA/ TN/ TR/ TON, SAFE FLEX, FLEX T, SAFE SM 0,8 to 1,25 UB
FA1 over ASI-Bus
Clearance and creeping distance
DIN EN 50178, or DIN VDE 0160 at pollution grade 2, over voltage category 3/300V
max. switching voltage
SAFE IL2 : 12 A AC, cos φ = 1
RS-NAGMP/MP.1 : 8 A AC, cos φ = 1; 8 A DC, τ =0
SAFE IRZ.2, SAFE 1/ 1.1/ 4/ 4.1/ M: 5 A AC, cos φ = 1; 5 A DC, τ =0
SAFE IL1, SAFE IL L, SAFE IL Z, RS-NAGV: 4 A AC, cos φ = 1; 4 A DC, τ =0
RS-NAGU.2f: 6 A DC (1 Kontakt), τ = 0
RS-NAGU.1/RS-NAGU.12: 1,5 A DC (1 Kontakt), τ = 0
SAFE C1, SAFE CL, SAFE CM, SAFE CZ: 1,8 A DC
Other : 6 A AC, cos φ = 1; 6 A DC, τ =0
Protection classes
Space requirements : IP 54
Housing : IP 40
Terminal area : IP 20
Mechanical life time
10
7
switching cycles
Electronical life time
10
5
switching cycles
Mounting
DIN rail EN 50022 ( 35 mm )
Pay attention to housing with detachable terminal strips: if you would like to detach the terminal strips please take away the power first.
The ground wire has to be connected to terminal PE when an auxillary voltage used (at the terminals A1 and A2) UB~ / whit galvanic
disconnection to connect a protective conductor. By AC/DC or DC - devices is this not permitted.
All operating instructions can be found under www.automation-safety.com
Developement
Production
Special advantages
emergency stop according to EN60204
redundant positiv guided relay
cyclical monitoring of the function
housing with detachable terminal strip
(for a quick change of the devices) by the
NAG-line (without RS-NAGU.1 / RS-NAGU.2f /
RS-NAGU.1f / RS-NAGU.12)
wireless layout
housing of self extinguishing plastic according
to UL 94-V1
100% computer assisted check
Testing area
NORSTAT INC. 300 Roundhill Dr. Rockaway, NJ 07866 Tel: 973-586-2500 Fax: 973-586-1590 www.norstat.com