Installation Guide

59
Cold Water Supply Pipe
Size the cold water supply piping to allow for
maximum flow rates of the building.
• Be sure to connect the cold water supply pipe
between the hot water storage tank and intake
side of the storage tank recirculation pump.
When installing 2 pumps in parallel
Storage Tank
Recirculation Pump 1
Storage Tank
Recirculation Pump 2
(If necessary)
Gas Pipe
Hot Water
Storage
Tank
Return Line
Recirculation Pump
Hot Water Return Line
Hot Wate
r
Supply
Remote Controller
ThermostatPump Control Wires
(Use external relays)
Water Heater 6Water Heater 2
Storage Tank Supply Line
(1 1/4 in.-2 in.)
(Size for max. flow)
Storage Tank Return Line
Water Heater 1
System Controller
(1 1/4 in.-2 in.)
(Size for max. flow)
Relief Valve
Hot Water Supply Line
The pump will push water through the Multi-System to heat up the tank.
When the temperature of the thermostat is high, the system controller will turn off the pump until
the temperature cools down.
Use copper or stainless water piping for the entire system.
For the set temperature of the Remote Controller, use the temperature (of the thermostat) +
about 10°F.
To achieve the highest recovery, size the storage tank recirculation pump for maximum capacity.
NOTE
9 GPM (each) @ 40 ft of head (160°F setting or less) + piping losses through the
system.
Verify the supply pressure to the Water Heaters is at least 30 psi.
17.1.3 Example of Installation with a Storage Tank and a Recirculation System
(Tank recirculation system)