Installation Guide

18
Use only solid PVC / CPVC (schedule 40) or PP
pipe.
2 in. or 3 in. schedule 80 pipe may also be used
on this Water Heater, however the Btu/h input of
the Water Heater will be reduced by up to 9%.
Maintain the same vent pipe diameter from the
Water Heater flue to the termination.
In Canada, plastic vent systems must be certified
to ULC S636. The components of the certified
vent system must not be interchanged with other
vent systems or unlisted pipe/fittings.
In Canada, specified primers and glues of the ULC
S636 certified vent system must be from a single
system manufacturer and not intermixed with
other system manufacturers vent system parts.
6.2.2 Installation Instructions
NOTE
Covering non-metallic vent pipe and
fittings with thermal insulation is
prohibited.
When preparing and assembling the pipe,
follow instructions as provided by the pipe
manufacturer. In general, the following practices
must be observed:
- Squarely cut all pieces of pipe.
- Remove all burrs and debris from joints and
fittings.
- All joints must be properly cleaned, primed,
and cemented. Use only cement and primer
approved for use with the pipe material as
outlined on page 17.
PVC, CPVC or PP pipe has been approved for
use on this Water Heater with zero clearance to
combustibles.
The pipe shall be installed so that the first 3 ft
(0.9 m) of pipe from the Water Heater flue outlet
is readily accessible for visual inspection.
When attaching the piping to the Water Heater,
use the appropriate primer and cement to ensure
a proper seal.
CARBON MONOXIDE POISONING
Failure to properly seal the vent system could
cause flue products to enter the living space.
WARNING
Follow all general venting guidelines as outlined in
this manual.
Clearance described in this document is the
minimum recommendation/required distance.
Take appropriate clearance according to the
situations of the site.
Make sure the vent system is gas tight and will
not leak.
Support the vent pipe with hangers at regular
intervals as specified by these instructions or the
instructions of the vent manufacturer.
All piping must be fully supported. Use pipe
hangers at a minimum of 3 ft (0.9 m) intervals.
NOTE
Do not use the Water Heater to
support the vent piping.
Ensure at least 3 ft (0.9 m) or more distance
between the near edge of the air intake pipe or
exhaust pipe to the inside corner of a wall.
Inside corner
3 ft (0.9 m)
or more
[How to tighten the Vent Pipe]
1. Continue to insert the Vent Pipe until it reaches
to the base of the Water Heater Exhaust and
Intake Flue.
The Vent Pipe will be inserted approximately
2.3 in. (60 mm).
2. Secure the Vent Pipe by tightening the band
using a screwdriver.
• The tightening torque shall be the following:
- For PVC/CPVC pipe: between 16 and 20 in lb
- For PP pipe: between 12 and 15 in lb
Exhaust and
Intake Flue
Screwdriver
- Flat head
- Box wrench (5/16 in.)
Vent Pipe
6.2.3 Termination Considerations
Steam or condensed water may come out from
the vent termination. Select the location for
the termination as to prevent injury or property
damage.
If snow is expected to accumulate, make sure the
termination will not be covered with snow or hit
by falling lumps of snow.
Venting the Water Heater