Instructions / Assembly
26
Vertical Vent Termination with Polypropylene N-Flex system
•
•
•
•
•
Terminate at least 3’ (0.9m) from the
combustion air intake of any appliance
and any other building opening.
Enclose exterior vent systems below
the roof line to limit condensation and
protect against mechanical failure.
When the vent penetrates a floor or
ceiling and is not running in a fire rated
shaft, a firestop and support is required.
When the vent termination is located not
less than 8' (2.4m) from a vertical wall or
similar obstruction, terminate above the
roof at least 2' (0.6m), but not more than
6' (1.87m), in accordance with the National
Fuel Gas Code ANSI Z223.1/NFPA 54.
The aluminum flex pipe serves as
protection against damage.
Firestop
Support
Firestop / Support
Storm
Collar
Roof
Flashing
Exhaust
2" Flexible
polypropylene pipe
Alminum
flex pipe
Intake
Flex Vent 2"
Conversion Kit
(EZ2-CK)
Flex Vent 2" Conversion Kit (EZ2-CK)
Refer to the instructions provided with "Flex Vent 2"
Conversion Kit" for additional detail.
This unit is suitable only for vertical vent.
WARNING