Instructions / Assembly

24
Flex Vent 2" Conversion Kit (EZ2-CK) must be
used when using 2" exible polypropylene pipe
for vent pipe installation. Refer to the instructions
provided with Flex Vent 2" Conversion Kit for
ad
ditional detail.
Under normal conditions, this appliance will
not produce an exhaust flue temperature in
excess of 149°F.
Refer to page 23 for additional requirements.
Make sure the vent system is gas tight and
will not leak.
Do not common vent or connect more than
one appliance to this venting system.
The total vent length including vertical vent runs
should be no less than 5' (1.5m).
Do not store hazardous or ammable substances
near the vent termination and check that the
termination is not blocked in any way.
Steam or condensed water may come out
from the vent termination. Select the location
for the termination so as to prevent injury or
property damage.
If snow is expected to accumulate, take care
the end of the pipe is not covered with snow
or hit by falling lumps of snow.
General Requirements
Clearances
2" exible polypropylene pipe has been approved
for use on this appliance with zero clearance to
combustibles.
Maximum Vent Lengths
Be sure to do
Maximum Vent Length varies according
to Vent Kit model.
Check the Vent Kit model.
Vent Kit
Max. Straight Vent Length
Flex Vent 2" Kit 25 feet
(EZ2FVK-1)
Dark gray
25' (7.5m)
Flex Vent 2" Kit 35 feet
(EZ2FVK-2)
Light gray
35' (10.5m)
* Max. number of 45 degree elbows : 2
- Not including Rigid 45 Elbow Set included in
this kit.
- No 90° elbows
* Max. Straight Vent Length numbers do not
include termination.
* Refer to Flex Vent 2" Kit installation manual for
additional requirements.
This appliance has been designed to be
vented with 2" exible polypropylene pipe.
Do not exceed the following maximum vent
lengths: