English Installation Supplement

Combustible Materials
4.3 It is essential for safety to ensure the following clearances to combustible materials are maintained.
See Diagrams 2 & 3 and table below.
Model
Clearances to Combustible Materials
Side (D) Back (E)
Bergen 400mm 200mm
Duo 400mm 100mm
Uno 500mm 150mm
Smarty 500mm 250mm
Quadro 550mm 200mm
Orion 600mm 600mm
4. Clearances continued
5. Flue
Diameter Minimum (mm) Height Minimum (M) Draught Optimum (Pa)
All Models 150mm 4.5m 12
Thetablebelowshowstheminimumrequirementsfortheueconditions.SeePage15oftheTechnicalAppendixformoredetailedinformation
regardingueconditions.
VENTILATION
A) Traditionally Built Homes
•Whereleakageisgreaterthan5m
3
/hour/m
2
.
•Ventilationnormallyrequired=550mm
2
per kW output over 5kW
B) Modern Construction Homes
•Whereleakageislessthan5m
3
/hour/m
2
.
•Ventilationnormallyrequired=550mm
2
per kW
Model
Bergen
Duo
Uno
Smarty
Quadro
Orion
A Additional Ventilation
mm
2
N/R N/R N/R N/R 660 990
cm
2
N/R N/R N/R N/R 6.6 9.9
B Additional Ventilation
mm
2
2750 2750 2200 2750 3410 3740
cm
2
27.50 27.50 22.00 27.50 34.10 37.40
6. Ventilation
In the UK depending on the age of the building construction it will be necessary to provide additional ventilation to the room housing the
appliance. The table below shows the required ventilation for each Nordpeis model.
For full details on ventilation see the Technical Appendix on Page 16.
Freestanding Stoves
10