E. Inrush Current 
Test Result 
: 
Test condition  Spec.  Reading 1  Reading 2  Reading 3 
 230Vac / 100 % Load  80A Max.  58.6A  57.5A  57.1A 
F. Over Voltage Protection 
Test Result 
: 
Test condition  Spec.  Reading 1  Reading 2  Reading 3 
 115Vac / 100 % Load Vout*(110%~150%) 115% 116% 116% 
 230Vac / 100 % Load Vout*(110%~150%) 115%  116%  115% 
G. Over Current Protection 
Test Result 
: 
Test condition  Spec.  Reading 1  Reading 2  Reading 3 
 115Vac / 100 % Load Iout*(110%~150%) 124% 123% 124% 
 230Vac / 100 % Load  Iout*(110%~150%) 122%  122%  125% 
H. Short Circuit Protection 
Test Result 
: 
Test condition  Spec.  Reading 1  Reading 2  Reading 3 
 115Vac / 100 % Load Auto Recovery  OK  OK  OK 
 230Vac / 100 % Load  Auto Recovery  OK  OK  OK 
I.  Input Power Consumption(No Load) 
Test Result 
: 
Test condition  Spec.  Reading 1  Reading 2  Reading 3 
 230Vac / 0 % Load 
≦ 0.5 W 
0.314W 0.313W 0.309W 
J. Power Factor 
Test Result 
: 
Test condition  Spec.  Reading 1  Reading 2  Reading 3 
 115Vac / 100 % Load
≧ 0.9 
0.994 0.994 0.993 
 230Vac / 100 % Load 
≧ 0.9 
0.948 0.947 0.947 