Control Panel Transformer - Primary +15-0-230-400 VAC
Standard control panel transformers with mounting brackets and terminals designed according to the
following specifications.
Specifications:
Power:
Frequency:
Primary:
Secondary:
Isolation:
Temp. class:
Approvals:
50 - 1000 VA
50/60 Hz
+15-0-230-400 VAC
12-0-12, 24-0-24, 55-0-55 or
0-230 VAC
4 kV RMS
B (130°)
EN61558-2
High quality safety and isolating transformers designed for use in control circuits and general
applications
Low noise laminations
Dual standard primary winding 230/400V ac with +15V tap for input flexibility
Dual secondary centre tapped. Earth terminal provided
Varnish impregnated for overall protection against humidity and rusting
Fully shrouded cage clamp terminal with voltage markings
Detailed product specification on permanent label
High efficiency, low regulation design
100% electrical and flash tested
Technical specification
Rated
Regulation
Overall Size Fixing Fixing
Wt.
VA % Typ L x W x H Centers Dia. Kg.
50 9 84 x 84 x 91 64 x 64 4.5 1.9
100 7.5 84 x 97 x 91 64 x 72 4.5 2.5
150 6 108 x 90 x 110 84 x 72 6.5 3.5
200 4 108 x 114 x 110
84 x 92 6.5 5
300 5 120 x 143 x 130
90 x 106 6.5 6.9
500 2.5 120 x 143 x 130
90 x 106 6.5 7.5
1000 2 150 x 175 x 155
122 x 132
7 14.6