Manual
6 Parameterisation 
BU 0180 GB-0914  Pre-series version  77 
Parameter list - inverter functions (selection) 
Parameter 
Description 
Factory 
setting 
Settings / functions (selection) 
P102  
Start-up time 
Start-up time (acceleration ramp) is the 
time corresponding to the linear 
frequency rise from 0 Hz to the set 
maximum frequency (P105). 
[2.00] 
Note: Values < 0.1 must be avoided 
P103  
Deceleration 
time 
The braking time (braking ramp) is the 
time corresponding to the linear 
frequency reduction from the set 
maximum frequency (P105) to 0Hz. 
[2.00] 
Note: Values < 0.1 must be avoided 
P104  
Minimum 
frequency 
The minimum frequency is the 
frequency supplied by the FI as soon as 
it is enabled and no additional setpoint 
is set. 
[0] 
P105  
Maximum 
frequency 
Is the frequency provided by the FI after 
it has been enabled and the maximum 
setpoint value is available. 
[50] 
P200  
motor list 
If a 4-pole NORD motor is used, the 
preset motor data can be called up. 
[0] 
Select appropriate motor power 
P201 – P208 
Motor data 
If a 4-pole NORD motor is not used, the 
motor data on the rating plate must be 
entered here. 
[xxx] 
Data according to rating plate 
P220  
Parameter 
identification 
The motor data is automatically 
determined by the FI with this 
parameter. 
[0] 
01= only stator resistance 
02= motor identification 
P400  
Setpoint input 
function 
Definition of the functions of the various 
setpoint inputs 
Input selection: 
AIN1 (P400, [-01]) 
AIN2 (P400, [-02]) 
[xxx] 
00= no function 
01= setpoint frequency 
P420  
Digital input 
functions 
Definition of the functions of the various 
digital inputs 
Input selection: 
DIN 1 (P420, [-01]) 
DIN 2 (P420, [-02]) 
DIN 3 (P420, [-03]) 
[xxx] 
00= no function 
01= enable right 
02= enable left 
04= fixed frequency 1 
P428 
Automatic 
starting 
Inverter enable with "Mains On" 
[0] 
0= Off (enable with flank) 
1= On (enable with level) 
Note: one digital input must be 
programmed and set to enable. 
P465  
Fixed frequency / 
Fixed frequency 
array 
Definition of fixed frequency values 
Selection: 
Fixed frequency 1 (P465, [-01]) 
Fixed frequency 2 (P465, [-02]) 
[xxx] 
P509 
Source Control 
Word 
Selection of the interface via which the 
FI is controlled. 
[0] 
00= Control terminals or keyboard 
01= Only control terminals 
03= System bus 
P523 
Factory setting 
Frequency inverter is restored to the 
factory setting 
[0] 
00= No change 
01= Load factory setting 