Manual
SK 180E Manual for frequency inverters     
68  Pre-series version  BU 0180 GB-0914 
5.2.3 Commissioning examples 
All  devices  can  be  operated  in  the  condition  in  which  they  are  delivered.  The  standard  motor  data  of  a 
4-pole IE1  standard asynchronous motor  of the  same power are  parameterised. The PTC  input  must  be 
bypassed, if a motor with PTC is not available. Parameter (P428) must be changed if an automatic start-up 
with "Mains On" is required. 
5.2.3.1  Minimal configuration 
The frequency inverter provides all the necessary low voltages (24V DC / 10V DC). 
Function 
Setting 
Setpoint 
External 10 kOhm potentiometer 
Controller enable 
External switch S1 
Minimal configuration with options 
In order to implement completely autonomous operation (i.e. independent of control cables etc.) a 
potentiometer unit (SK CU4-POT) is required. In this way, the required speed and direction control can be 
achieved with only a single mains cable (single phase or three-phase, according to the version) (see 
connection example in Section 3.3.1). 
5.3 KTY84-130 connection 
The  current  vector  control  of  the  SK  1x0E  series  can  be  further  optimised  by  the  use  of  a  KTY84-130 
temperature sensor (R
th(0°C)
=500, R
th(100°C)
=1000). By continuous measurement of the motor temperature, 
the highest precision of regulation by the frequency inverter and the associated optimum speed precision of 
the motor is achieved at all times. As the temperature measurement starts  immediately after the (mains) 
switch-on of the frequency inverter, the frequency inverter provides immediate optimum control, even if the 
motor  has  a considerably increased  temperature after an intermediate  "Mains off / Mains on" of the 
frequency inverter. 
Connection examples: 
SK 1x0E 
Connection of a KTY-84 to either of the two analog inputs of the SK 1x0E is possible. In the following examples, 
analog input 2 of the frequency inverter is used. 
1.  The motor data P201-P207 must be set according to the rating plate. 
2.  The motor stator resistance P208 is determined at 20°C with P220 = 1. 
3.  Function analog input 2, P400 [-02] = 30 (Motor temperature) 
4.  The mode analog input 2 P401 [-06] = 1 (negative temperatures are 
also measured)  
Adjustment of analog input 2: P402 [-06] = 1.54V and  
P403 [-06] = 2.64V (with R
V
= 2.7 kOhm) 
5.  Adjust time constants: P404 [-02] = 400ms 
(Filter time constant is maximum) 
6.  Motor temperature control (display): P739 [-03] 
* If necessary, also Terminal 40 
Frequency inverter 
SK 1x0E-... 
Control terminal bar 
12/40 
14  
11 
. 
43 
. 
21 
22 
. 
38 
39 
L1 - L2/N - L3 
230/400 V 
1/3~ 230/400V + PE 
Switch S1 
Motor PTC 
Potentiometer 
10kOhm 