5 Commissioning 
5.1 Factory settings 
All  frequency  inverters  supplied  by  Getriebebau  NORD  are  pre-programmed  with  the  default  setting  for 
standard  applications  with  4-pole  standard  motors  (same  voltage  and  power).  For  use  with  motors  with 
other  powers  or number  of  poles,  the  data  from  the rating  plate  of the  motor  must be  input  into the 
parameters P201...P207 under the menu item >Motor data<. 
NOTE:  All motor data can be pre-set using parameter P200. After use of this function, this parameter 
is reset to 0 = no change! The data is loaded automatically into parameters P201...P209  – 
and can be compared again with the data on the motor rating plate. 
3~ Mot 
IEC 56 
IM B3 
cos 0.74 
cos 0.74 
IP55 
Rot. KL 16 
Th.Cl.F 
EN60034 
60 Hz 
460 V Y 
5.2 A 
2,5 kW 
1765 /min 
1440 /min 
P206 
P201 
P204 
P203 
P202 
P200 
9,0 / 5.2 A 
50 Hz 
2.2 kW 
P207 
P200 Motor list: 
  0 = no change  10 = 0.37 kW 230 V 
1 = no motor  11 = 0.50 PS 230 V  
  2 = 0.12 kW 230 V  12 = 0.37 kW 400 V 
  3 = 0.16 PS 230 V  13 = 0.50 PS 460 V 
  4 = 0.18 KW 230 V  14 = 0.55 kW 230 V 
  5 = 0.25 PS 230 V  15 = 0.75 PS 230 V 
  6 = 0.25 kW 230 V  16 = 0.55 kW 400 V 
  7 = 0.33 PS 230 V  17 = 0.75 PS 460 V 
  8 = 0.25 kW 400 V  18 = 0.75 kW 230 V 
  9 = 0.33 PS 460 V  .... 
 230 / 400 V /Y 
RECOMMENDATION:  For the correct operation of the drive unit, it is necessary to input the motor data 
(rating plate) as precisely as possible. In particular, an automatic stator resistance 
measurement using parameter P220 is recommended. 
In order to automatically determine the stator resistance, set P220 = 1 and confirm 
by pressing "OK".  The value  calculated for  the line  resistance (dependent  upon 
P207) will be saved in P208. 
5.2 Commissioning of frequency inverters 
The frequency inverter can be commissioned  by adjustments to the parameters with software,  using 
ParameterBox  (SK CSX-3H  or  SK PAR-3H)  or  the  PC-based  software  NORD  CON.  Here,  the 
parameterised data is stored in the internal EEPROM.  
ATTENTION 
DANGER TO LIFE! 
The frequency inverter is not equipped with a line main switch and is therefore always live when 
connected to the power supply. Live voltages may therefore be connected to a connected motor 
at standstill. 