Manual
SK 180E Manual for frequency inverters     
54  Pre-series version  BU 0180 GB-0914 
3.3 Details of internal Customer Units SK CU4-… 
3.3.1 Potentiometer adapter, SK CU4-POT 
The digital signals R and L can be directly applied to the corresponding digital inputs 1 and 2 or 3 of the 
frequency inverter.  
The  potentiometer  (0-10V)  can  be  evaluated  via  the  analog  inputs  of  the  frequency  inverter,  or  via  an 
optional I/O extension. 
Module 
SK CU4-POT 
Function 
SK 1x0E 
Pin 
Color 
FI 
1 
brown 
24V-supply voltage 
43 
Rotary switch 
L - OFF - R 
2 
black 
Enable R (e.g. DIN1) 
21 
3 
white 
Enable L (e.g. DIN2) 
22 
4 
white 
Access to AIN + 
14 
Potentiometer 
10kΩ 
5 
brown 
Reference voltage 10V 
11 
6 
blue 
Analog ground AGND 
12 
SK CU4-POT connections 
Frequency inverter 
SK 1x0E-... 
Control terminal bar 
12(40) 
14 
11 
. 
. 
43 
. 
. 
21 
22 
. 
. 
SK CU4-POT 
Potentio-
meter 
0-10 
R/0/L 
Switch 
L1 - L2/N - L3 
230/400V 
24V= 
10V= 
(A)GND 
0-10V 
R 
L 
1/3~ 230/400V + PE 
(br) 
(br) 
(bk) 
(wh) 
(br) 
(wh) 