Manual
SK 180E Manual for frequency inverters     
28  Pre-series version  BU 0180 GB-0914 
2.4 Overvoltage filter SK CIF 
The use of a suitable ("CSA-") overvoltage filter is mandatory (see also Section 1.5) in order to comply with 
cUL requirements. For 230V devices, operation of the frequency inverter with a suitable overvoltage filter is 
only permissible if a mains choke is used in addition. 
For  further  information  about  the  overvoltage  filter,  please  refer  to  the  relevant  data  sheet.  These  data 
sheets can be downloaded at www.nord.com. 
Inverter ID 
Filter type 
Data sheet 
SK 1x0E-250-323-A… SK 1x0E-111-323-A* 
SK CIF-323-20 
(alternatively SK CIF-323-40) 
TI 030 276997070 
(TI 030 276997071) 
SK 1x0E-250-340-A… SK 1x0E-221-340-A 
SK CIF-340-30 
(alternatively SK CIF-340-60) 
TI 030 276997080 
(TI 030 276997081) 
* (only with suitable mains choke) 
Without  an  overvoltage  filter,  frequency  inverters  for  1~  115V  mains  (SK1x0E-xxx-112-O)  cannot  be 
approved according to cUL. 
CAUTION! 
Modules SK CIF-323-x0 may only be used in combination with a suitable mains choke 
(L
min 
= 3 x 0,73 mH) (see connection diagram). 
For SK CIF-340-x0 modules the use of a mains input choke is not mandatory, but is recommended. 
Note 
With the use of a mains choke, the effective input currents of the 1~ 230V frequency inverter reduce 
to approximately the values of the output currents. Several frequency inverters can be connected to 
a choke - filter combination. In this case, the total input currents must not exceed the current rating 
of the filter. 