Manual
SK 180E Manual for frequency inverters     
130  Pre-series version  BU 0180 GB-0914 
Parameter 
Setting value / Description / Note 
Device 
Supervisor 
Parameter 
set 
P715 
Running time 
(Enablement time)  
0.00 ... ___ h 
This parameter shows the time for which the FI was enabled and supplied current to the output. 
P716 
Actual frequency 
(Actual frequency)  
-400.0 ... 400.0 Hz 
Displays the actual output frequency. 
P717 
Actual speed 
(Actual rotation speed)  
-9999 ... 9999 rpm 
Displays the actual motor speed calculated by the FI. 
P718  [-01] 
  ... 
  [-03] 
Current set freq. 
(Actual setpoint frequency)  
-400.0 ... 400.0 Hz 
Displays the frequency specified by the setpoint. 
[-01] = Actual setpoint frequency from the setpoint source 
[-02] = Actual setpoint frequency after processing in the FI status machine 
[-03] = Actual setpoint frequency after frequency ramp 
P719 
Actual current 
(Actual current)  
0.0 ... 999.9 A 
Displays the actual output current. 
P720 
Act. torque current 
(Actual torque current)  
-999.9 ... 999.9 A 
Displays the actual calculated torque-developing  output  current (active  current). Basis for 
calculation are the motor data P201...P209. 
 negative values = generator,  positive values = drive 
P721 
Actual field current 
(Actual field current)  
-999.9 ... 999.9 A 
Displays the actual calculated field current (reactive current). Basis for calculation are the motor 
data P201...P209. 
P722 
Actual voltage 
(Actual voltage) 
0 ... 500 V 
Displays the actual AC voltage supplied by the FI output. 
P723 
Voltage -d  
(Actual voltage component Ud)  
S 
-500 ... 500 V 
Displays the actual field voltage component. 
P724 
Voltage -d  
(Actual voltage component Ud)  
S 
-500 ... 500 V 
Displays the actual torque voltage component. 
P725 
Actual cos phi 
(Actual cos )  
0.00 ... 1.00 
Displays the actual calculated cos  of the drive. 
P726 
Apparent power 
(Apparent power)  
0.00 ... 99.99 kVA 
Displays  the  actual  calculated  apparent  power.  Basis  for  calculation  are  the  motor  data 
P201...P209. 