Manual
6 Parameterisation 
BU 0180 GB-0914  Pre-series version  105 
Parameter 
{Factory setting} 
Setting value / Description / Note 
Device 
Supervisor 
Parameter 
set 
18 = FI ready: The FI is ready for operation. After being enabled it delivers 
an output signal. 
High 
19 = ... 29 reserved 
30 = Digital-In 1 status* 
High 
Details for the 
use of the 
relevant bus 
systems can be 
found in the 
applicable 
supplementary 
bus manual. 
31 = Digital-In 2 status* 
High 
32 = Digital-In 3 status* 
High 
33 = Status Digital-In 4 / A-In1 * 
High 
34 = Status Digital-In 5 / A-In2 * 
*) (P546[-01]…[-03]) = 20 
P435  [-01] 
  [-02] 
Dig. out scaling  
(Scaling of digital output)  
-400 ... 400 % 
{ 100 } 
[-01] =  Digital output 1, Digital output 1 of the frequency inverter 
[-02] =  Digital output 2, Digital output 2 of the frequency inverter 
Adjustment of the limiting values of the output function. For a negative value, the output function 
will be output negative. 
Reference to the following values: 
Current limit (3) = x [%]  P203 >Rated motor current< 
Torque current limit (4) = x [%]  P203  P206 (calculated rated motor torque) 
Frequency limit (5) = x [%]  P201 >Rated motor frequency< 
P436  [-01] 
  [-02] 
Dig. out. hysteresis  
(Hysteresis of digital outputs)  
S 
1 ... 100 % 
{ 10 } 
[-01] =  Digital output 1, Digital output 1 of the frequency inverter 
[-02] =  Digital output 2, Digital output 2 of the frequency inverter 
Difference between switch-on and switch-off point to prevent oscillation of the output signal. 
P460 
Time watchdog 
(Time watchdog)  
S 
0.0  /  0.1  ...  250.0  s 
-0.1 ... -250.0 sec 
{ 10.0 } 
0.1 ... 250.0 = The  time  interval  between  the  expected  Watchdog  signals  (programmable 
function of the digital inputs P420 – P425). If this time interval passes without a 
pulse being registered, a switch off occurs with an E012 error message. 
0.0 = Customer error: As soon as a high-low flank or a low signal is detected at a digital input 
(function 18) the FI switches off with error message E012.    
-0.1 ... -250.0 =  In this case the rotor rotation watchdog is active The time is defined by the 
amount of the set value. There is no watchdog message when switched off. 
After each enable, a puls must first come before the watchdog is activated. 