6 Parameterisation 
BU 0180 GB-0914  Pre-series version  103 
Value 
Function 
Description 
Signal 
74 ² 
Left block+ Fast 
"Block left rotation + emergency 
stop" 
As for setting 32, however coupled to the function "Fast Stop". 
Low 
75 
Dig.out. 2 man/auto set 
"Set digital output 2 manually / 
automatically" 
As for function 67, however for digital output 2 
High 
76 
Dig.out. 2 man. set 
"Set digital output 2 manually" 
As for function 68, however for digital output 2 
High 
77 
Reserved  
1
  If neither of the digital inputs is programmed for left or right enable, then the actuation of a fixed frequency or jog frequency will 
enable the frequency inverter. The rotation field direction depends on the sign of the setpoint. 
2
  Also effective for bus control (RS232, RS485, CANbus, CANopen, DeviceNet, Profibus, InterBus, AS-Interface) 
3
  Function cannot be selected via BUS IO In Bits 
Parameter 
{Factory setting} 
Setting value / Description / Note 
Device 
Supervisor 
Parameter 
set 
P426 
Quick stop time 
(Quick stop time)  
S 
P 
0 ... 320.00 sec 
{ 0.10 } 
Setting of the stop time for the fast stop function which can be triggered either via a digital input, 
the bus control, the keyboard or automatically in case of a fault. 
Emergency  stop  time  is  the  time  for  the  linear  frequency  decrease  from  the  set  maximum 
frequency (P105) to 0Hz. If an actual setpoint <100% is being used, the emergency stop time is 
reduced correspondingly. 
P427 
Emerg. stop on error 
(Emergency stop on fault) 
S 
0 ... 3 
{ 0 } 
Activation of automatic emergency stop following error 
0 = Disabled: Automatic emergency stop following fault is deactivated 
1 = Mains supply failure: Automatic emergency stop following mains supply failure 
2 = In case of faults: Automatic emergency stop following error 
3 = Fault or mains failure:  Automatic emergency stop in case of fault or mains failure 
P428 
Automatic start 
(Automatic start)  
S 
0 ... 1 
{ 0 } 
In the standard setting (P428 =0  Off) the inverter requires a flank to enable (signal change 
from "low high") at the relevant digital input. 
In the setting  On  1 the FI reacts to a High level. This function is only possible if the FI is 
controlled using the digital inputs. (see P509=0/1) 
In certain cases, the FI must start up directly when the mains are switched on. For this P428 = 1 
 On can be set. If the enable signal is permanently switched on,  or equipped with a cable 
jumper, the FI starts up immediately. 
NOTE:  (P428) not "ON" if (P506) = 6, Danger! (See note on (P506)) 
NOTE:  The "Automatic Start" function can only be used if a digital input of the frequency 
inverter (DIN 1 … DIN 4) is parameterised to the function "Enable Right" or "Enable 
Left" and this input is permanently set to "High". The digital inputs of the technology 
units (e.g.:SK CU4 - IOE) do not support this "Automatic Start" function. 
NOTE:  The "Automatic Start" function can only be activated if the frequency inverter has 
been parameterised to local control ((P509) setting { 0 } or { 1} ). 