GB BU 0180 SK 180E…190E BU 0180 GB-0914 Manual for Frequency inverters 1
SK 180E Manual for frequency inverters About this document NORD frequency inverters Safety and operating instructions for drive power converters (as per: Low Voltage Directive 2006/95/EEC) 1.General During operation, drive power converters may, depending on their protection class, have live, bare, moving or rotating parts or hot surfaces. Unauthorised removal of covers, improper use, incorrect installation or operation causes a risk of serious personal injury or material damage.
SK 180E Manual for frequency inverters About this document Documentation Designation: BU 0180 GB Part No.: 607 1801 Device series: SK 180E, SK 190E Device types: SK 1x0E-250-112-O ... SK 1x0E-750-112-O, 0.25 - 0.75 kW, 1~ 100-120 V, Output. 230 V SK 1x0E-250-323-B ... SK 1x0E-111-323-B, 0.25 - 1.1 kW, 1/3~ 220-240 V SK 1x0E-151-323-B, 1.5 kW, 3~ 220-240 V SK 1x0E-250-340-B ... SK 1x0E-221-340-B, 0.25 – 2.
SK 180E Manual for frequency inverters About this document Intended use of the frequency inverter Compliance with the operating instructions is essential for fault-free operation and the acceptance of any warranty claims. These operating instructions must be read before working with the device! These operating instructions contain important information about servicing. They must therefore be kept close to the device.
Table of Contents 1 GENERAL .................................................................................................................................8 1.1 Overview ...............................................................................................................9 1.2 Delivery .................................................................................................................9 1.3 Scope of supply ..............................................................................
SK 180E Manual for frequency inverters 3 OPTIONS................................................................................................................................ 49 3.1 Overview of optional modules ........................................................................... 50 3.1.1 Overview of internal customer units SK CU4-… ..................................................... 50 3.1.2 Overview of external technology units SK TU4-… .................................................. 51 3.
Table of Contents 8 TECHNICAL DATA ...............................................................................................................151 8.1 General data for frequency inverter series SK 1x0E ........................................151 8.2 Electrical data for frequency inverter ................................................................152 8.2.1 Electrical data 1~115V .......................................................................................... 153 8.2.
SK 180E Manual for frequency inverters 1 General The SK 1x0E series is based on the tried and tested NORD platform. These devices feature a compact design with optimum control characteristics. These devices are provided with sensorless vector current control system which in combination with asynchronous three-phase motor types constantly ensures an optimised voltage-to-frequency ratio. This has the following significance for the drive: Peak start-up and overload torques at constant speed.
1 General 1.1 Overview Basic features of the SK 180E / SK 190E: High starting torque and precise motor speed control setting with sensorless current vector control Can be installed directly on, or near to the motor.
SK 180E Manual for frequency inverters Extension modules: internal SK CU4-IOE, internal I/O extension SK CU4-PBR, internal PROFIBUS DP® module SK CU4-CAO, internal CANopen® module SK CU4-DEV, internal DeviceNet™ module SK CU4-ECT, internal EtherCAT® module (Note: Derating) SK CU4-PNT, internal PROFINET IO® module (Note: Derating) SK CU4-POL, internal POWERLINK module (Note: Derating) SK CU4-EIP, internal Ethernet/IP™ module (Note: Derating) SK CU4-POT , Potentiometer adapter: internal potentiometer/switch
1 General 1.4 Safety and installation information The frequency inverters are equipment for use in industrial high voltage systems and are operated at voltages that could lead to severe injuries or death if they are touched. Installation and other work may only be carried out by qualified electricians and with the device disconnected. The operating instructions must always be available to these persons and must be strictly observed.
SK 180E Manual for frequency inverters CAUTION The heat sink and all other metal components can heat up to temperatures above 70°C. When mounting, sufficient distance from neighboring components must be maintained. When working on the components, allow sufficient cooling time beforehand Protection against accidental contact may need to be provided. ATTENTION The power unit can continue to carry voltages for up to 5 minutes after being switched off at the mains.
1 General 1.5 Certifications 1.5.1 European EMC Directive If the frequency inverter is installed according to the recommendations in this manual, it meets all EMC directive requirements, as per the EMC product standard for motor-operated systems EN 61800-3. (See also Section 9.3 Electromagnetic Compatibility [EMC].) 1.5.2 UL and cUL approval (in preparation) The section applies for all devices of sizes 1 – 2. All frequency inverters are equipped with motor overload protection.
SK 180E Manual for frequency inverters cUL Approval - File No. E171342 “cUL only in combination with SK CIF-340-30 or SK CIF-340-60 for 380-480V models and SK CIF-323-20 or SK CIF-323-40 for 3 phase 200-240V rated models”. The recognized transient surge suppression filter board has to be connected between supply and the input of the drive according to the instruction manual.
1 General 1.6 Nomenclature / type codes Unique type codes have been defined for the individual modules and devices. These provide individual details of the device type, its electrical data, protection class, fixing version and special versions.
SK 180E Manual for frequency inverters 1.6.1 Type code / Frequency inverter - Basic device SK 180E-370-323-B (-C) IP protection class: Standard = IP55, C = “coated” = IP66 Radio interference filter: O = without, A = Class A1 (C2), B = Class B1 (C1) Mains voltage: x12 = 115 V, x23 = 230 V, x40 = 400 V Number of mains phases: 1xx = single phase, 3xx = 3-phase (for 230V up to 1.1kW: 1~/3~) Digits before decimal point for power: 0 = 0.xx, 1 = 0x.x0, 2 = 0xx.0 Device nominal power: 250 = 0.25 kW, 370 = 0.
1 General 1.7 Version with protection class IP55 / IP66 The frequency inverters and additional modules are available in protection classes IP55 (standard) or IP66 (optional). The protection class IP66 must always be stated when ordering! There are no restrictions or differences to the scope of functions in either protection class. In order to differentiate the protection classes, modules with protection class IP66 are given an extra “-C” (coated coated PCBs) in their type designation. e.g.
SK 180E Manual for frequency inverters 2 Assembly and installation 2.1 Installation and assembly The frequency inverters are available in various sizes depending on their output. They can be mounted on the terminal box of a motor or in its immediate vicinity. Motor-mounted version Wall-mounted version NOTE The equipment requires sufficient ventilation to protect against overheating.
2 Assembly and installation 2.1.1 Mounting the housing box On delivery of a complete drive unit (gear unit + motor + frequency inverter) the frequency inverter is always fully installed and tested. NOTE Installation of an IP66-compliant frequency inverter must be carried out by NORD, as special measures have to be implemented. IP66 components retrofitted on site cannot ensure that this protection class is guaranteed.
SK 180E Manual for frequency inverters 2.1.2 Adapters for different motors In some cases, the terminal box attachments are different for different sizes of motor. Therefore, it may be necessary to use an adapter to mount the frequency inverter. In order to guarantee the maximum protection class IP55 / IP66 of the entire unit, motor must also have a corresponding protection class.
2 Assembly and installation 2.1.3 Installation of the frequency inverter The housing cover must first be removed in order to make the electrical connections to the frequency inverter. To do this, unscrew the 4 fastening screws, so that the housing cover can be removed upwards. After the electrical connections of the supply cables have been made, the housing cover can be replaced.
SK 180E Manual for frequency inverters 2.1.4 Option slots in the device Size 1: 1 1 3R 3L 4L 3AL 3BR 3BL 4R 3AR 5R 5L Size 2: 2 1 1 2 3R 3AR 3BR 3L 4L 3AL 3BL 4R 5R 5L The above drawings indicates the different installation locations for optional modules. Option slot 1 is used for the mounting of an internal customer interface (e.g. bus module). Option location 2 for installing an internal brake resistor is only present in size 2.
2 Assembly and installation 2.2 Dimensions of the frequency inverter 2.2.1 Power rating / Motor size Mains / Power category SK 1x0E Size 1~ 110-120 V 1~, 3~ 200-240 V 3~ 380-480 V Size I 0.25 ... 0.75 kW 0.25 ... 0.55 kW 0.25 ... 1.1 kW Size II - 0.75 ... 1.5 kW 1.5 ... 2.2 kW * 1.5 kW only 3~ 2.2.2 Motor-mounted frequency inverter Size FI Size I Housing dimensions SK 1x0E / Motor Weight of SK 2xxE without motor Motor g g1 Size 71 * 145 177.5 Size 80 165 171.
SK 180E Manual for frequency inverters 2.2.3 Wall-mounted frequency inverter The frequency inverter can be installed in the vicinity of the motor by means of an optional wall mounting kit. Device type Wall-mounting Housing dimensions total weight SK TIE4-WMK-L-1 Size Approx. [kg] g2 n p p2 d e Size 1 SK TIE4-WMK-1 Part No. 275 274 000 113 221 154 205 64 180 5.5 2.6 Size 2 SK TIE4-WMK-1 Part No. 275 274 000 115,5 255 165 205 64 180 5.5 3.
2 Assembly and installation 2.3 Brake resistor (BR) (only size 2) During dynamic braking (frequency reduction) of a three phase motor, electrical energy is returned to the frequency inverter. From Size II or larger, an internal or external brake resistor may be used to prevent the FI from shutting down in case of overvoltage. With this, the integrated brake chopper (electronic switch) pulses the link circuit voltage (switching threshold approx.
SK 180E Manual for frequency inverters 2.3.2 External brake resistor SK BRE4-... The external brake resistor (available for SK 1x0E, Size 2) is intended for energy feedback, e.g. in pulse drives or lifting gear. Here, it may be necessary to plan for the exact brake resistor required. For installation, an M20 screw connection with an adapter for M25 is supplied. The connecting wires for the brake resistor are fed through this into the connection unit.
2 Assembly and installation 2.3.4 Electrical data BR Internal Inverter ID SK 1x0E-… 750…111-323-A Resistor type (IP54) SK BRI4-1-200-100 Resistance 200 Max. continuous Energy output / limit** consumption* (Pn) (Pmax) 100 W / 25% 1.0 kWs Part. No. 275272008 151…221-340-A SK BRI4-1-400-100 Connecting cable or terminals Silicone conductor 2x 0.75 mm 400 100 W / 25% 1.0 kWs Part. No. 275272012 2 approx.
SK 180E Manual for frequency inverters 2.4 Overvoltage filter SK CIF The use of a suitable ("CSA-") overvoltage filter is mandatory (see also Section 1.5) in order to comply with cUL requirements. For 230V devices, operation of the frequency inverter with a suitable overvoltage filter is only permissible if a mains choke is used in addition. For further information about the overvoltage filter, please refer to the relevant data sheet. These data sheets can be downloaded at www.nord.com.
2 Assembly and installation 2.5 Wiring guidelines The frequency inverter has been developed for use in an industrial environment. In this environment, high levels of electromagnetic interference can influence the frequency inverter. In general, correct installation ensures safe and problem-free operation. To meet the limiting values of the EMC directives, the following instructions should be complied with.
SK 180E Manual for frequency inverters 2.6 Electrical connection WARNING THE DEVICES MUST BE EARTHED. Safe operation of the devices requires that is installed and commissioned by qualified personnel in compliance with the instructions provided in this Manual. In particular, the general and regional installation and safety regulations for work on high voltage systems (e.g. VDE) must be complied with, as must the regulations concerning correct use of tools and the use of personal protection equipment.
2 Assembly and installation 2.7 Electrical connection of power unit L1 / L L2 / N L3 / PE All connection terminals are located in the connection unit of the frequency inverter. Separate terminal bars are provided for the power connections and the control connections, as well as a further terminal bar for the connection of the thermistor. The PE connections (device earth) are located on the power connections for the motor and the mains, as well as on the base in the cast housing.
SK 180E Manual for frequency inverters 2.7.1 Mains supply (L1, L2, L3, PE) No special safety measures are required on the mains input side of the frequency inverter. It is advisable to use normal mains fuses (see technical data) and a main switch or circuit breaker. 115V devices may only be used with a 110…120V (L/N = L1/L2) single phase supply. 230V devices can optionally be used for single phase or three-phase operation. 400V devices are designed for three phase mains voltage 380...480V (L1/L2/L3).
2 Assembly and installation 2.7.3 Brake resistor connection (-B, +B) (only size 2) The terminals +B/ -B are intended for the connection of a suitable braking resistor (only size 2). The connection should be as short as possible. Connection cross-section: 2 0.2 ... 4/6mm rigid/ flexible cable AWG 24-10 B+, B- Starting torque: 0.5 ... 0.6 Nm Note: The great production of heat in the braking resistor must be taken into account. 2.7.
SK 180E Manual for frequency inverters 2.8 Electrical connection of the control unit The control connections are located on the inside of the frequency inverter housing. The connections to the terminal bar differ according to the version (SK 180E…190E). Connection terminals: Spring-loaded terminal (X4, X5), slot-head screwdriver, size 2.0 mm PCB terminal with screw connection (X3), size 2.0 mm, 0.5...0.6 Nm 2 Connection cross-section: 0.2...1.
2 Assembly and installation 2.8.
SK 180E Manual for frequency inverters 2.8.2 Control connection details The frequency inverter generates its own control voltage and provides this to Terminal 43. Terminal/ Function Designation {Factory setting} 43 24V supply VO/24V Data Description / wiring suggestion Parameter - Output 24V DC ±25% 40 21 GND / 0V DIN1 max.
2 Assembly and installation Terminal/ Function Designation {Factory setting} 77 System bus+ 78 SYS H SYS L System bus- Data Description / wiring suggestion Parameter Up to four SK 1x0E or SK 2xxE can be operated on a single system bus. Internal FI system bus for communication with optional modules and other frequency inverters. P509/510 Address = 32 / 34 / 36 / 38 S1 P514/515 For further details see Section 9.6.
SK 180E Manual for frequency inverters 2.8.3 Control connections, communication Terminal/ Designation Function {Factory setting} Data Description / wiring suggestion Parameter all devices, plug connector block RJ12, RS485/RS232 Data cable RS232 5 232 RXD 6 +24V (for connection to a PC for NORDCON) 24 V voltage supply from FI RX D P502 ...
2 Assembly and installation 2.9 Plug connectors The use of optionally available plug connectors for power and control connections not only makes it possible to replace the drive unit more quickly in case of servicing, but also minimises the danger of installation errors when connecting the device. The most common plug connector versions are summarized below. The possible mounting locations on the housing box are listed in Section 2.1.4. 2.9.
SK 180E Manual for frequency inverters Assembly Mounting of a plug connector on the housing of the frequency inverter is usually only possible with a connection adapter (connection extension SK TIE4-HAN10E). Plug connector* Part. No. Technical data plus SK TIE4-HAN10E (275274100) HAN 10E LA 2BUE 275135010 Add-on housing with 2-clamp lock, socket insert 10-pin. + PE, spring terminals, PE: Screw connection, electrical data: 16A 500V X 275135070 Add-on housing with 1-clamp lock, pin insert 10-pin.
2 Assembly and installation 2.9.2 Plug connectors for control connection Various M12 round plug connectors are available as flanged plugs or flanged sockets. The plug connectors are intended for installation in the housing box of the frequency inverter and can be oriented as required. The protection class (IP67) of the plug connector only applies in the screwed state. The cover caps correspond to the colour version as does the plastic body of the plug connector.
SK 180E Manual for frequency inverters System components Description Data AS Interface A-coded, 5-pin PIN 1 PIN 2 PIN 3 PIN 4 PIN 5 SK TIE4-M12-ASI Part. No. 275274502 M12 flanged plug to connect an AS interface cable ASi+ (/+24V) n. c. ASi- (/GND) n. c. n. c. (brown) (blue) Plastic body in yellow PROFIBUS DP B-coded, 5-pin SK TIE4-M12-PBR Part. No. 275274500 M12 flanged plug to connect the incoming PROFIBUS DP cable PIN 1 PIN 2 PIN 3 PIN 4 PIN 5 +5V* PBR-A GND * PBR-B n. c.
2 Assembly and installation 2.10 ATEX Zone 22 for frequency inverters (in preparation) General information With appropriate modification, the frequency inverter can be used in explosion hazard areas. For this it is important that all the safety information in the operating instructions is strictly complied with for the prevention of personal injury and material damage. This is essential to prevent injury and damage.
SK 180E Manual for frequency inverters 2.10.1 Modified frequency inverter for compliance with Category 3D Operation of the frequency inverter in ATEX Zone 22 is only possible with appropriate modifications. This adaptation is only made at the NORD factory. In order to use frequency inverters in ATEX Zone 22, among other things, the diagnostic caps are replaced with aluminium / glass versions.
2 Assembly and installation 2.10.2.
SK 180E Manual for frequency inverters Wire colors on the potentiometer Designation Terminal SK CU4-24V* Terminal SK CU4-IOE Terminal SK 1x0E red +10V reference [11] [11] [11] black AGND / 0V [12] [12] [12] / [40] green Analog input [14] [14] / [16] [14] / [16] 2.10.2.3 Hand-held Technology Units for ATEX Zone 22 3D All hand-held technology units are not approved for continuous use in the ATEX Zone 22 3D.
2 Assembly and installation 2.10.2.5 Other options M12 sockets and plugs for installation in the terminal box of the basic device or in technology units may only be used if they are approved for use in ATEX Zone 22 3D.
SK 180E Manual for frequency inverters 2.10.4 Commissioning information For Zone 22 the cable glands must at least comply with protection class IP 55. Unused openings must be closed with blank screw caps suitable for ATEX Zone 22 3D (minimum protection class IP 55). The motors are protected against overheating by means of the frequency inverter. This is carried out by the evaluation of the motor PTC by the frequency inverter.
3 Options 3 Options The frequency inverter provides a series of optional expansion modules. These modules are preferably used for the direct control or connection of the frequency inverter to a higher level field bus. The options are available both as an internal version for integration (into the FI), the so-called customer unit SK CU4-...
SK 180E Manual for frequency inverters 3.1 Overview of optional modules 3.1.1 Overview of internal customer units SK CU4-… Internal customer interfaces enable the expansion of the range of functions of the frequency inverter without changing its physical size. For example, either a field bus module or an I/O extension can be selected. The frequency inverter provides one slot for the fitting of an appropriate option.
3 Options 3.1.2 Overview of external technology units SK TU4-… External technology units enable the modular extension of the scope of frequency inverter functions. Users have access to both communication modules and an internal mains unit or an I/O expansion and other modules. Bus modules with connection terminals or M12 system connectors are available as options. Modules with protection class IP55 or optionally IP66 can be ordered according to the installation location.
SK 180E Manual for frequency inverters Type PROFINET IO IP55 IP66 M12 X X X X I/O extension X X X X X X X X Designation Part Number Document SK TU4-PNT SK TU4-PNT-C SK TU4-PNT-M12 SK TU4-PNT-M12-C SK TU4-IOE SK TU4-IOE-C SK TU4-IOE-M12 SK TU4-IOE-M12-C 275 281 115 275 281 165 275 281 122 275 281 172 275 281 106 275 281 156 275 281 206 275 281 256 TI 275281115 TI 275281165 TI 275281122 TI 275281172 TI 275281106 TI 275281156 TI 275281206 TI 275281256 Required accessories (each module must have
3 Options 3.2 Mounting of optional module 3.2.1 Installation of internal customer units SK CU4-… WARNING Installation must be carried out by qualified personnel only, paying particular attention to safety and warning instructions. Modules must not be inserted or removed unless the device is free of voltage. The slots may only be used for the intended modules. Installation of the SK CU4-… customer unit remote from the frequency inverter is not permitted.
SK 180E Manual for frequency inverters 3.3 Details of internal Customer Units SK CU4-… 3.3.1 Potentiometer adapter, SK CU4-POT The digital signals R and L can be directly applied to the corresponding digital inputs 1 and 2 or 3 of the frequency inverter. The potentiometer (0-10V) can be evaluated via the analog inputs of the frequency inverter, or via an optional I/O extension. Module SK CU4-POT Function SK 1x0E Pin Color 1 brown 24V-supply voltage 43 2 black Enable R (e.g.
3 Options 3.3.2 Electronic brake rectifier, SK CU4-MBR The electronic brake rectifier SK CU4-MBR is used to control electromechanical brakes with a coil voltage of 180V DC and 205V DC (for sizes 5Nm to 40Nm via the frequency inverter or its accessories (SK xU4-IOE). Monitoring of the current in the brake coil is integrated into the SK CU4-MBR module.
SK 180E Manual for frequency inverters Control connection details Terminal/ Function Data Description / wiring suggestion Parameter Designation 44 24V 24V supply - 24 V DC ± 25% 40 GND /0V C5 DIN GND Reference potential Digital input 50 … 500mA (according to load on the digital output) Current consumption with 30 V DC: 13 mA 24 V DC: 10 mA 15 V DC: 5.5 mA Supply voltage connection for the module - Digital input for DC brake switching - Switching thresholds ON: > approx. 8.
3 Options 3.3.3 Setpoint converter, SK CU4-REL The analog inputs of SK 1x0 E series frequency inverters and the optional mains units SK xU4-24V can only process unipolar setpoint values referenced to GND (0/2 … 10 V; 0/4 … 20 mA). If a bipolar setpoint (10V … + 10 V) is available, this must be converted to a 0 … 10 V signal by means of an SK CU4-REL setpoint converter. Two coupling relays are integrated into the module.
SK 180E Manual for frequency inverters To separate the two potential levels, the jumper (at the start of the series terminal) must be plugged in differently or pulled out entirely.
3 Options 3.3.4 Direction selection switch and potentiometer SK TIE4-SWT and SK TIE4-POT The digital signals R and L of the direction selector switch SK TIE4-SWT (Part No.: 275274701) can be applied directly to the corresponding digital inputs 1 and 2 of the frequency inverter. The potentiometer (0-10 V) SK TIE4-POT (Part No.: 275274700) can be evaluated via the analog inputs of the frequency inverter or the I/O extension. Each of the modules (control element) is supplied with a pre-assembled cable.
SK 180E Manual for frequency inverters 3.4 Details of external Technology Units SK TU4-… The technology units are divided into two different groups. The BUS group contains all the bus modules and the I/O extension. These are connected to the SK 1x0E via the system bus. The second group includes other technology units, e.g. the maintenance switch SK TU4-MSW. Due to the very different functions, the device groups require different connection units. 3.4.
3 Options 3.4.1.1 Connections of the SK TI4-TU-BUS The precise connections of the 36 spring-loaded terminals depend on the Technology Unit used. Details can be found in the relevant documents for the bus system. 3.4.1.2 Connections of the SK TI4-TU-MSW Connection of the incoming and outgoing mains cable (incl. PE) is made on the relevant terminal blocks as shown in the illustration. With single phase mains cables the conducting phase must be connected to L1 and the neutral conductor to L2.
SK 180E Manual for frequency inverters 3.4.2 Maintenance switch, SK TU4-MSW-… The maintenance switch can be looped into the mains supply cable of the frequency inverter in order to interrupt the voltage supply to a connected frequency inverter. The maintenance switch has a 3-pole design and can therefore be used for 1 - 3 phase AC supply networks up to 480 V UNom.
4 Display and control 4 Displays and control By the use of various modules for display, control and parameterisation, the frequency inverter can be easily adapted to various requirements. Alphanumeric display and control modules (Section 4.2) can be used for simple commissioning. For more complex tasks, connection to a PC system and the use of NORD CON parameterisation software is available. As supplied, without additional options, the diagnostic LED is externally visible.
SK 180E Manual for frequency inverters 4.2 Overview of external control devices All parameters can be easily accessed for reading or editing by means of an optional SimpleBox or ParameterBox. The changed parameter data are stored in the non-volatile EEPROM memory. In addition, up to 5 complete frequency inverter data sets can be saved in the ParameterBox and then recalled. The connection between the SimpleBox or ParameterBox and the SK 1x0E is made with an RJ12-RJ12 cable.
5 Commissioning 5 Commissioning 5.1 Factory settings All frequency inverters supplied by Getriebebau NORD are pre-programmed with the default setting for standard applications with 4-pole standard motors (same voltage and power). For use with motors with other powers or number of poles, the data from the rating plate of the motor must be input into the parameters P201...P207 under the menu item >Motor data<. NOTE: All motor data can be pre-set using parameter P200.
SK 180E Manual for frequency inverters NOTE For commissioning standard applications, a limited number of the frequency inverter inputs and outputs (physical and I/O bits) have predefined functions. These settings may need to be changed (Parameters (P420), (P434), (P480), (P481)). 5.2.1 Connection After mounting the frequency inverter on the motor or the wall mounting kit, the mains and motor cables must be connected to the relevant terminals (PE, L1, N (/L2, L3) and U, V, W) (See sections 2.7 and 2.8).
5 Commissioning 5.2.2.2 DIP switch configuration of the inverter The analog inputs in the frequency inverter are suitable for current and voltage setpoints. For correct processing of current setpoints (0-20mA / 4-20mA) the relevant DIP switch (S1) must be set for current signals ("ON"). No. Bit DIP switch (S1) 3 U / I AIN2 2 Voltage/current 2 U / I AIN1 2 Voltage/current 1 SYS 2 1 20 0 1 0 1 0 1 Burden resistor Analog input 2 in voltage mode 0...10 V Analog input 2 in current mode 0/4...
SK 180E Manual for frequency inverters 5.2.3 Commissioning examples All devices can be operated in the condition in which they are delivered. The standard motor data of a 4-pole IE1 standard asynchronous motor of the same power are parameterised. The PTC input must be bypassed, if a motor with PTC is not available. Parameter (P428) must be changed if an automatic start-up with "Mains On" is required. 5.2.3.
5 Commissioning SK CU4-IOE / SK TU4-IOE-… Connection of a KTY-84 to either of the two analog inputs of the relevant option is possible. In the following examples, analog input 2 of the particular optional module is used. SK CU4-IOE SK TU4-IOE (Illustration shows a section of the terminal blocks) Parameter settings (Analog input 2) The following parameters must be set for the function of the KTY84-130. 1. The motor data P201-P207 must be set according to the rating plate. 2.
SK 180E Manual for frequency inverters 5.4 AS interface (only SK 190E) 5.4.1 The bus system The ActuatorSensor Interface (AS-Interface) is a bus system for the lower field bus level. The transmission principle is a single master system with cyclical polling. A maximum of 31 slaves (or 62 A/B slaves in the extended address region) can be operated on an up to 100m long unshielded two-wire cable in any network structure (tree/line/star). For the AS-interface, since the Complete Specification V2.
5 Commissioning 5.4.3 Bus structure and topology The AS interface network can be set up in any desired form. Linear, star, ring and tree structures are possible. An existing network can be expanded by further slaves at any time. Up to 31 standard slaves (i.e. a maximum of 124 binary sensors and 124 binary actuators) or 62 A/B slaves (i.e. a maximum of 248 binary sensors and 248 binary actuators) can be connected to an AS interface network or an AS interface master.
SK 180E Manual for frequency inverters 5.4.4 Commissioning of the AS Interface Connection Connection of the AS interface cable is made via terminals 85/85 of the terminal block and can optionally be made to an appropriately labelled M12 flange plug contact (yellow) Details of the connection terminals are explained in Section 2.8.2. 85 84 Signal status LED / ASi-specific display With these devices, the status of the ASi interface is indicated by the dual colour LEDAS-i.
5 Commissioning Procedure for SK 190E: Ensure power supply of the ASi interface via the yellow ASi cable. Disconnect the AS-i master during addressing Set the address ≠ 0 Do not doubly assign addresses Normal hand-held units can be used for the addressing of the frequency inverter. Typical manufacturers are Pepperl+Fuchs (e.g.: VBP-HH1-V3.0-V1) and IFM (E.g.: AC1154). The following lists the possibilities for the practical implementation of addressing an SK 190E with an addressing box.
SK 180E Manual for frequency inverters 5.4.5 Technical data for AS interface Designation Value Supply via AS interface connection PWR connection (yellow cable) Slave profile S-7.A I/O-Code 7 ID Code A External ID Code 1 / 2 7 1A – 31A and 1B - 31B (condition as delivered: 0A) Address 74 24 V, max.
6 Parameterisation 6 Parameterisation The frequency inverter, field bus and I/O -extension modules each have their own logic systems. These can be adapted to customers' requirements by means of changeable parameters. The basic functions of the particular modules are factory-set, so that the units have basic functionalities on delivery. Limited adaptations of individual functions of the relevant devices can be implemented vie DIP switches.
SK 180E Manual for frequency inverters If the SimpleBox SK CSX-3H is used, the array level is shown by _ - 0 1 . With the ParameterBox SK PAR3H (picture on right) the selection options for the array level appear at the top right of the display. ParameterBox SK PAR-3H SimpleBox SK CSX-3H P50 2 ENTER P_ 0 1 ENTER OFF ENTER OFF Setting: Value of master function 1 VALUE P_ 0 2 Setting: Value of master function 2 6.
6 Parameterisation Parameter list - inverter functions (selection) Parameter Factory setting Description Settings / functions (selection) P102 Start-up time Start-up time (acceleration ramp) is the time corresponding to the linear frequency rise from 0 Hz to the set maximum frequency (P105). [2.00] Note: Values < 0.1 must be avoided P103 Deceleration time The braking time (braking ramp) is the time corresponding to the linear frequency reduction from the set maximum frequency (P105) to 0Hz. [2.
SK 180E Manual for frequency inverters Parameter list - inverter information (selection) Parameter P700 Actual operating status Description Display of current messages for the actual operating status of the frequency inverter such as faults, warnings or the cause of a switch-on block.
6 Parameterisation 6.1.1 Operating displays The abbreviations used are described in Section 9.12 “Abbreviations in this Manual". Parameter {Factory setting} P000 0.01 ... 9999 P001 Setting value / Description / Note Device Supervisor Parameter set Operating para. disp. (Operating parameter display) In the SimpleBox (SK CSX-3H) display, the parameter value online selected in P100 is displayed. Selection display (Selection display) 0 ...
SK 180E Manual for frequency inverters Parameter {Factory setting} P002 Setting value / Description / Note Device Parameter set Supervisor Display factor S (Display factor) 0.01 ... 999.99 { 1.00 } The selected operating value in parameter P001 >Select of display< is multiplied with the scaling factor in P000 and displayed in >Operating parameter display<. It is therefore possible to display system-specific operating such as e.g.
6 Parameterisation Parameter {Factory setting} P101 0 ...
SK 180E Manual for frequency inverters Parameter {Factory setting} P106 0 ... 100 % {0} Setting value / Description / Note Device Supervisor Ramp smoothing Parameter set S (Ramp smoothing) P This parameter enables a smoothing of the acceleration and deceleration ramps. This is necessary for applications where gentle, but dynamic speed change is important. Ramp smoothing is carried out for every setpoint change.
6 Parameterisation Parameter {Factory setting} P107 0 ... 2.50 s { 0.00 } Setting value / Description / Note Device Supervisor Brake reaction time Parameter set P (Brake reaction time) Electromagnetic brakes have a physically-dependent delayed reaction time when actuated. This can cause a dropping of the load for lifting applications, as the brake only takes over the load after a delay. This reaction time can be taken into account under parameter (P107).
SK 180E Manual for frequency inverters Parameter {Factory setting} P108 0 ... 13 {1} Setting value / Description / Note Disconnection mode (Disconnection mode) Device Supervisor Parameter set S P This parameter determines the manner in which the output frequency is reduced after "Blocking" (controller enable low). 0 = Voltage block: The output signal is switched off immediately. The FI no longer supplies an output frequency. In this case, the motor is braked only by mechanical friction.
6 Parameterisation Parameter {Factory setting} P109 Setting value / Description / Note DC brake current Device Supervisor S (DC brake current) Parameter set P 0 ... 250 % Current setting for the functions of DC current braking (P108 = 3) and combined braking (P108 = 5). { 100 } The correct setting value depends on the mechanical load and the required deceleration time. A higher setting brings large loads to a standstill more quickly.
SK 180E Manual for frequency inverters Parameter {Factory setting} Setting value / Description / Note Device Supervisor Jog frequency P113 S (Jog frequency) -400.0 ... 400.0 Hz { 0.0 } Parameter set P When using the SimpleBox or ParameterBox to control the FI, the jog frequency is the initial value following successful enabling. Alternatively, when control is via the control terminals, the jog frequency can be activated via one of the digital inputs.
6 Parameterisation 6.1.3 Motor data / characteristic curve parameters Parameter {Factory setting} P200 Setting value / Description / Note Device Supervisor Motor list Parameter set P (Motor list) 0 ... 51 Adjustment of the motor data from a list for 4-pole IE1 DS standard motors. {0} By selecting one of the possible digits and pressing the OK key, all motor parameters (P201…P209) are adjusted to the selected standard power.
SK 180E Manual for frequency inverters Parameter {Factory setting} P204 100 ... 800 V {] P205 0.00 ... 150.00 kW *** { } P206 0.50 ... 0.90 *** { } P207 0 ... 1 *** { } P208 0.00 ... 300.00 *** { } Setting value / Description / Note Device Supervisor Nominal motor voltage (Nominal motor voltage) S Parameter set P The >Nominal voltage< matches the mains voltage to the motor voltage. In combination with the nominal frequency, the voltage/frequency characteristic curve is produced.
6 Parameterisation Parameter {Factory setting} P212 0 ... 150 % { 100 } Setting value / Description / Note Slip compensation (Slip compensation) Device Supervisor S Parameter set P The slip compensation increases the output frequency, dependent on load, to keep the asynchronous motor speed approximately constant. The factory setting of 100% is optimal when using DC asynchronous motors and correct motor data has been set.
SK 180E Manual for frequency inverters Parameter {Factory setting} P217 0 ... 400 % { 10 } Setting value / Description / Note Oscillation damping (Oscillation damping) Device Supervisor S Parameter set P With the oscillation damping, idling current harmonics can be damped. Parameter 217 is a measure of the damping power. For oscillation damping the oscillation component is filtered out of the torque current by means of a high pass filter.
6 Parameterisation Parameter {Factory setting} P2xx Setting value / Description / Note Device Supervisor Parameter set Control/characteristic curve parameters Output voltage P204 P211 P210 P215 P201 P216 Time NOTE: "typical" Settings for the...
SK 180E Manual for frequency inverters 6.1.4 Control terminals Parameter {Factory setting} P400 [-01] ... [-07] Setting value / Description / Note Device Supervisor Parameter set Fnct. setpoint inputs P (Function of setpoint inputs) 0 ... 36 { [-01] = 1 } { [-02] = 0 } { [-03] = 0 } { [-04] = 0 } { [-05] = 0 } { [-06] = 0 } { [-07] = 0 } [-01] = Analog input 1, Function of analog input 1 integrated into the FI [-02] = Analog input 2, Function of analog input 2 integrated into the FI [-03] = Ext.
6 Parameterisation Parameter {Factory setting} Setting value / Description / Note Device Supervisor Parameter set 16 = Torque precontrol, a function that enables a value for the anticipated torque requirement to be entered in the controller (interference factor switching). This function can be used to improve the load take-up of lifting equipment with separate load detection. 17 = Multiplication, the setpoint is multiplied with the analog value supplied.
SK 180E Manual for frequency inverters Parameter {Factory setting} Setting value / Description / Note Device Supervisor Parameter set 1 = 0 – 10 V: If a setpoint smaller than the programmed adjustment 0% (P402) is present, this may cause a change in the direction of rotation. This allows rotation direction reversal using a simple voltage source and potentiometer. E.g.
6 Parameterisation Parameter {Factory setting} Setting value / Description / Note Device Supervisor Parameter set At the moment of reversal (hysteresis = P505), the drive stands still when the minimum frequency (P104) is smaller than the absolute minimum frequency (P505). A brake which is controlled by the FI has not been applied in the hysteresis range. If the minimum frequency (P104) is greater than the absolute minimum frequency (P505), the drive reverses when the minimum frequency is reached.
SK 180E Manual for frequency inverters Parameter {Factory setting} P402 [-01] ... [-06] Setting value / Description / Note Device Supervisor Adjustment: 0% Parameter set S (Analog input adjustment: 0%) -50.00 ... 50.00 V [-01] = Analog input 1, Function of analog input 1 integrated into the FI { all 0.00 } [-02] = Analog input 2, Function of analog input 2 integrated into the FI [-03] = Ext. Analog input 1, AIN1 of the first I/O extension (SK xU4-IOE) [-04] = Ext.
6 Parameterisation Parameter Setting value / Description / Note {Factory setting} Device Supervisor Parameter set P400 ... P403 Output frequency Output frequency P105 P105 positive positive P104 P104 z.B. 0,0 V 2,5 V 5,0 V P402 P404 [-01] [-02] 10,0 V Setpoint voltage P403 z.B. negative Analog input filter 0,0 V 2,5 V P402 5,0 V 10,0 V Setpoint voltage P403 S (analog input filter) 10 ... 400 ms Adjustable digital low-pass filter for the analog signal.
SK 180E Manual for frequency inverters Parameter {Factory setting} Setting value / Description / Note Device Setpoint process controller P412 (Setpoint value for process controller) Supervisor Parameter set S P -10.0 ... 10.0 V Fixed specification of a setpoint for the process controller that will only occasionally be altered. { 5.0 } Only with P400 = 6 or 7 (PID process controller). Further details can be found in Section 9.2 .
6 Parameterisation Parameter {Factory setting} ... only with SK CU4-IOE or SK TU4-IOE Setting value / Description / Note Device Supervisor Parameter set Analog functions (max. load: 5mA analog): An analog voltage (0 ... +10 Volt) can be taken from the control terminals (max. 5mA). Various functions are available, whereby: 0 Volt analog voltage always corresponds to 0% of the selected value.
SK 180E Manual for frequency inverters Parameter {Factory setting} P419 [-01] [-02] Setting value / Description / Note Device Analog output scaling (Standardisation of analog output) Supervisor S Parameter set P -500 ... 500 % [-01] = First IOE, AOUT of the first I/O extension (SK xU4-IOE) { all 100 } [-02] = Second IOE, AOUT of the second I/O extension (SK xU4-IOE) ...
6 Parameterisation List of the possible functions of the digital inputs P420 [01]... [-04] Value Function Description Signal 00 No function Input switched off.
SK 180E Manual for frequency inverters Value 30 Function Description Disable PID Switching the PID controller / process controller function on and off (high = ON) Blocks the >Enable right/left< via a digital input or Bus control. Does not depend on the actual direction of rotation of the motor (e.g. following negated setpoint). 31 2 Disable right rotation 32 2 Disable left rotation 33 ... 44 reserved 45 3-W-Ctrl.
6 Parameterisation Value 74 ² Function Description Left block+ Fast "Block left rotation + emergency stop" 75 Dig.out. 2 man. set "Set digital output 2 manually" 77 1 As for setting 32, however coupled to the function "Fast Stop". Low As for function 67, however for digital output 2 High As for function 68, however for digital output 2 High Dig.out.
SK 180E Manual for frequency inverters Parameter {Factory setting} P434 [-01] [-02] Setting value / Description / Note Device Parameter set Digital output function (Digital output function) 0 ... 39 [-01] = Digital output 1, Digital output 1 of the frequency inverter { [-01] = 7 } [-02] = Digital output 2, Digital output 2 of the frequency inverter { [-02] = 1 } Supervisor Control terminals 1/40 (Section 2.8.2 ): The settings 3 to 5 and 11 work with 10% hysteresis, i.e.
6 Parameterisation Parameter {Factory setting} Setting value / Description / Note Device Supervisor Parameter set 18 = FI ready: The FI is ready for operation. After being enabled it delivers an output signal. High 19 = ... 29 reserved 30 = Digital-In 1 status* High 31 = Digital-In 2 status* High 32 = Digital-In 3 status* High Details for the use of the relevant bus systems can be found in the applicable supplementary bus manual.
SK 180E Manual for frequency inverters Parameter {Factory setting} Setting value / Description / Note Fixed frequency mode P464 (Fixed frequency mode) 0 ... 1 Device Parameter set Supervisor S This parameter determines the form in which fixed frequencies are to be processed. 0 = Addition to main setpoint: (Addition of the fixed frequency to the main setpoint) Fixed frequencies and the fixed frequency array are added to each other. I.e.
6 Parameterisation Parameter Setting value / Description / Note {Factory setting} P475 [-01] ... [-05] Device delay on/off switch Supervisor Parameter set S (Switch on/off delay) -30.000... 30,000 sec Adjustable on/off delay for the digital inputs. Use as a switch-on filter or simple process control is possible. { 0.
SK 180E Manual for frequency inverters Parameter {Factory setting} P481 [-01] ... [-10] 0 ... 39 Setting value / Description / Note Device Supervisor Parameter set )Funct. BusIO Out Bits (Function Bus I/O Out Bits The bus I/O Out bits are perceived as multi-function relay outputs. They can be set to the same functions (P434).
6 Parameterisation Parameter {Factory setting} P483 1 … 100 % [-01] ... [-10] Setting value / Description / Note Device ... Hyst. BusIO Out Bits Supervisor Parameter set S (Hysteresis of bus I/O Out bits) Difference between switch-on and switch-off point to prevent oscillation of the output signal.
SK 180E Manual for frequency inverters 6.1.5 Extra functions Parameter {Factory setting} Parameter set Free input of a designation (name) for the device (max. 20 characters). With this, the frequency inverter can be uniquely identified for setting with NORD CON - software or within a network. {0} { all 0 } Supervisor (Inverter name) A…Z (char) 0 ... 24 Device Inverter name P501 P502 Setting value / Description / Note [-01] ...
6 Parameterisation Parameter {Factory setting} P503 0 ... 3 {0} P504 3.0 ... 16.0 kHz { 6.0 } P505 0.0 ... 10.0 Hz { 2.0 } Setting value / Description / Note Leading func. output (Master function output) Device Supervisor Parameter set S For master-slave applications this parameter specifies on which bus system the master transmits the control word and the master values (P502) for the slave.
SK 180E Manual for frequency inverters Parameter {Factory setting} Setting value / Description / Note Device Supervisor Automatic error acknowledgement P506 S (Automatic fault acknowledgement) 0 ... 7 Parameter set In addition to the manual fault acknowledgement, an automatic acknowledgement can also be selected. {0} 0 = No automatic fault acknowledgement. 1 = ... 5 = Number of permissible automatic malfunction acknowledgments within one mains-on cycle.
6 Parameterisation Parameter {Factory setting} P511 0 ... 3 {3} P512 0 ... 30 {0} P513 -0.1 / 0.0 / 0.1 ... 100.0 s { 0.0 } Setting value / Description / Note Device Supervisor USS baud rate Parameter set S (USS baud rate) Setting of the transfer rate (transfer speed) via the RS485 interface. All bus participants must have the same baud rate setting. 0 = 4800 Baud 2 = 19200 Baud 1 = 9600 Baud 3 = 38400 Baud USS Address (USS Address) Setting of the FI Bus address.
SK 180E Manual for frequency inverters Parameter {Factory setting} P515 [-01] … ... [-03] Setting value / Description / Note Device CAN address (CAN address (system bus)) Supervisor Parameter set S 0 ... 255dec Setting of the system bus address.
6 Parameterisation Parameter {Factory setting} P520 0 ... 4 {0} Setting value / Description / Note Device Supervisor Flying start circuit Parameter set S (Flying start circuit) P This function is required to connect the FI to already rotating motors, e.g. in fan drives. Motor frequencies >100Hz cannot be captured. 0 = Switched off, no flying start. 1 = Both directions, the FI looks for a speed in both directions.
SK 180E Manual for frequency inverters Parameter {Factory setting} P525 [-01] ... [-03] Setting value / Description / Note Device Load monitoring max. (Load monitoring maximum value) 1 ... 400 % / 401 Selection of up to 3 auxiliary values: { all 401 } [-01] = Auxiliary value 1 [-02] = Auxiliary value 2 Supervisor S Parameter set P [-03] = Auxiliary value 3 Maximum load torque value. Setting of the upper limit of load monitoring. Up to 3 values can be specified.
6 Parameterisation Parameter {Factory setting} P528 0.10 ... 320.00 sec { 2.00 } Setting value / Description / Note Load monitoring Delay (Load monitoring Delay) Device Supervisor Parameter set S P Parameter (P528) defines the delay time for which an error message ("E12.5") is suppressed on infringement of the defined monitoring range ((P525) … (P527)). A warning ("C12.5") is triggered after half of this time has elapsed.
SK 180E Manual for frequency inverters Parameter {Factory setting} P525 … P529 Setting value / Description / Note Device Supervisor Parameter set Load monitoring With the load monitoring, a range can be specified within which the load torque may change depending on the output frequency. There are three auxiliary values for the maximum permissible torque and three auxiliary values for the minimum permissible torque. A frequency is assigned to each of these auxiliary values.
6 Parameterisation Parameter {Factory setting} Setting value / Description / Note Device Supervisor Factor I2t-Motor P533 Parameter set S 2 (Factor I t-Motor) 50 ... 150 % 2 The motor current for the I t motor monitoring P535 can be weighted with the parameter P533. Larger factors permit larger currents. { 100 } P534 [-01] [-02] 25 ... 400 % / 401 { all 401 } Torque disconn. limit S (Torque switch-off limit) Via this parameter both the drive [-01] and the generator adjusted.
SK 180E Manual for frequency inverters Parameter {Factory setting} P536 0.1 ... 2.0 / 2.1 (x nominal FI current) { 1.5 } Setting value / Description / Note Device Current limit Supervisor Parameter set S (Current limit) The inverter output current is limited to the set value. If this limit value is reached, the inverter reduces the actual output frequency. With the analog input function in P400 = 13/14, this limit value can also be varied and cause an error message (E12.4). 0.1 ... 2.
6 Parameterisation Parameter {Factory setting} P540 0 ... 7 {0} Setting value / Description / Note Device Supervisor Mode phase sequence Parameter set S (Mode phase sequence) P For safety reasons this parameter can be used to prevent a rotation direction reversal and therefore the incorrect rotation direction. This function does not operate with active position control (P600 ≠ 0).
SK 180E Manual for frequency inverters Parameter {Factory setting} Setting value / Description / Note Device Supervisor Set relay P541 S (set digital output) 000 ... FFF(hex) Parameter set This function provides the opportunity to control the relay and the digital outputs independently of the frequency inverter status. To do this, the relevant output must be set to the function "External control". { 000 } This function can either be used manually or in combination with a bus control.
6 Parameterisation Parameter {Factory setting} P543 [-01] ... [-03] Setting value / Description / Note Device Supervisor Actual bus value 1 3 S (Actual bus value 1 … 3) 0 ... 24 The return value can be selected for bus actuation in this parameter. { [-01] = 1 } NOTE: { [-02] = 4 } { [-03] = 9 } Parameter set P For further details, please refer to the relevant bus manual or the description for (P418).
SK 180E Manual for frequency inverters Parameter {Factory setting} P546 Setting value / Description / Note Device Parameter set Supervisor Func. bus-set point 1... 3 S (Function of bus setpoint 1 ... 3) P 0 ... 32 In this parameter, a function is allocated to the output setpoint during bus actuation. { [-01] = 1 } NOTE: { [-02] = 0 } { [-03] = 0 } For further details, please refer to the relevant bus manual or the description for (P400).
6 Parameterisation Parameter {Factory setting} P552 0 … 100 ms { all 2 } [-01] [-02] Setting value / Description / Note Device Supervisor CAN Master cycle Parameter set S (CAN Master cycle time)) In this parameter, the cycle time for the system bus master mode and the CAN open encoder is set (see P503/514/515): [01] = CAN Master function, Cycle time for system bus master functions [02] = CANopen Abs.
SK 180E Manual for frequency inverters Parameter {Factory setting} Setting value / Description / Note Brake resistor power P557 (Brake resistor power) 0.00 ... 20.00 kW { 0.00 } Device Only relevant for size 2 Supervisor Parameter set S Continuous power (nominal power) of the resistor, to display the actual utilisation in P737. For a correctly calculated value, the correct value must be entered into P556 and P557. 0.
6 Parameterisation 6.1.6 Information (Frequency inverter) Parameter P700 Setting value / Description / Note [-01] ... [-03] 0.0 ... 21.4 Device Supervisor Parameter set Actual operating status (Actual operating status) Display of current messages for the present operating status of the frequency inverter such as faults, warnings or the reason why switch-on is disabled. For details of the messages, see Section 7 [-01] = Present fault, shows the currently active (unacknowledged) fault (Section 7.2.
SK 180E Manual for frequency inverters Parameter P705 Setting value / Description / Note [-01] ... [-05] 0 ... 1000 V DC Device Supervisor DC-Link Voltage previous error 1...5 Parameter set S (DC-Link Voltage previous error 1...5) This parameter stores the link voltage that was being delivered at the time the error occurred. The values of the last 5 errors are stored. With the SimpleBox, the corresponding memory location 1...
6 Parameterisation Parameter P709 Setting value / Description / Note [-01] ... [-07] -100.0 ... 100.0 % Device Supervisor Parameter set Voltage analog input (Voltage of analog input) Displays the measured analog input value. [-01] = Analog input 1, Function of analog input 1 integrated into the FI [-02] = Analog input 2, Function of analog input 2 integrated into the FI [-03] = Ext. Analog input 1, AIN1 of the first I/O extension (SK xU4-IOE) [-04] = Ext.
SK 180E Manual for frequency inverters Parameter Setting value / Description / Note Supervisor Parameter set Running time P715 (Enablement time) 0.00 ... ___ h This parameter shows the time for which the FI was enabled and supplied current to the output. Actual frequency P716 (Actual frequency) -400.0 ... 400.0 Hz Displays the actual output frequency. Actual speed P717 (Actual rotation speed) -9999 ... 9999 rpm P718 Device [-01] ... [-03] -400.0 ... 400.
6 Parameterisation Parameter P727 -99.99 ... 99.99 kW P728 0 ... 1000 V P729 -400 ... 400 % P730 0 ... 250 % P731 0 ... 3 P732 0.0 ... 999.9 A Setting value / Description / Note 0.0 ... 999.9 A 0.0 ... 999.9 A Displays the actual calculated effective power of the motor. Basis for calculation are the motor data P201...P209. Input voltage (Input voltage) Displays the actual mains voltage at the FI input. Torque (Torque) Displays the actual calculated torque.
SK 180E Manual for frequency inverters Parameter Setting value / Description / Note Device Supervisor Parameter set Usage rate brake res. P737 (Actual brake resistor usage rate) 0 ... 1000 % This parameter provides information about the actual degree of modulation of the brake chopper or the current utilisation of the braking resistor in generator mode. If parameters P556 and P557 are correctly set, the utilisation related to P557, the resistor power, is displayed.
6 Parameterisation Parameter P741 Setting value / Description / Note [-01] ... [-10] 0000 ... FFFF (hex) Device Parameter set Supervisor Process data Bus Out S (Process data Bus Out) This parameter provides information about the actual status word and the actual values that are transferred via the bus systems. For standardisation of actual values: See also (Section 9.9).
SK 180E Manual for frequency inverters Parameter P748 Device Supervisor Parameter set CANopen status (CANopen status (system bus status)) 0000 ... FFFF (hex) Shows the status of the system bus. or Bit 0: 24V Bus supply voltage 0 ... 65535 (dec) Bit 1: CANbus in "Bus Warning" status Bit 2: CANbus in "Bus Off" status Bit 3: System bus → Bus module online (field bus module, e.g.: SK xU4-PBR) Bit 4: System bus → Additional module 1 online (I/O - module, e.g.
6 Parameterisation Parameter Setting value / Description / Note (Overcurrent statistic) 0 ... 9999 Stat. Overvoltage S S (Overvoltage statistic) 0 ... 9999 Number of overvoltage messages during the operating period P714. Stat. mains failure P752 S (Mains failure statistics) 0 ... 9999 Number of mains faults during the operating period P714. Stat. overtemperature P753 (Overheating statistics) 0 ... 9999 S Number of overtemperature faults during the operating period P714. Stat.
SK 180E Manual for frequency inverters 6.2 Parameterisation of I/O - extension SK xU4-IOE-… In order to access the parameters of the I/O extension, the parameterisation tool (ParameterBox, NORD CON) must be connected directly to the device. If the I/O extension is on an active system bus, it can be accessed with the ParameterBox SK PAR-3H or the NORD CON software as well as via another device (e.g. frequency inverter SK 1x0E).
7 Status messages Parameter {Factory setting} P161 0 ... 400.00 ms { [-01] = 100 } { [-02] = 100 } [-01] ... [-09] Setting value / Description / Note Device Supervisor Parameter set Filter time (Filter time) The analog and digital inputs are read cyclically every 250µs, this results in an input uncertainty of 0.25ms. In order to eliminate bounce and smooth the input signals, the information which is read in is passed through a filter routine.
SK 180E Manual for frequency inverters 6.2.2 Information (I/O - extension) Parameter P170 Setting value / Description / Note ... [-01] ... [-02] 0 ... 9999 Device Parameter set Supervisor Present error (Present error) Actual error present. Further details in Section 7 "Operating status messages".
7 Status messages Parameter Setting value / Description / Note Device Supervisor Parameter set Module status P173 (Status of the module) 0 ...
SK 180E Manual for frequency inverters 7 Operating status messages According to the cause, frequency inverters and technology units generate appropriate messages if they deviate from their normal operating status. There is a differentiation between warning and error messages. If the frequency inverter is in the status "Start disabled", the reason for this can also be displayed. Display of the Technology Unit messages is carried out via parameter (P170).
7 Status messages 7.1 SimpleBox display The SimpleBox displays an error with its number and the prefix "E". In addition, the current fault can be displayed in array element [-01] of parameter (P700). The last error messages are stored in parameter P701. Further information on inverter status at the time that the error occurs can be found in parameters P702 to P706 / P799.
SK 180E Manual for frequency inverters Display in the SimpleBox Group Details in P700[-01] / P701 E003 3.0 Fault Cause Text in the ParameterBox Remedy 2 2 I t overcurrent limit Rectifier I t limit has triggered, e.g. > 1,5 x In for 60s (Please also note P504) Continuous overload at inverter output 3.1 2 Chopper overtemperature I t 2 I t limit for brake chopper triggered (Only Size II) (1.
7 Status messages Display in the SimpleBox Group Details in P700[-01] / P701 E008 8.0 Fault Cause Text in the ParameterBox Remedy Parameter loss (maximum EEPROM value exceeded) Error in EEPROM data Software version of the stored data set not compatible with the software version of the FI. NOTE: Faulty parameters are automatically reloaded (default data). EMC interferences (see also E020) 8.1 Inverter type incorrect EEPROM faulty 8.2 External copying error -- 8.
SK 180E Manual for frequency inverters Display in the SimpleBox Group Details in P700[-01] / P701 E010 10.0 Fault Cause Text in the ParameterBox Remedy Bus Timeout Data transfer is faulty. Check P513. (Telegram time-out / Bus off 24V int. CANbus) Check physical bus connections. Check bus protocol program process. Check Bus Master. Check 24V supply of internal CAN/CANopen Bus. Nodeguarding error (internal CANopen) Bus Off error (internal CANbus) 10.
7 Status messages Display in the SimpleBox Fault Cause Text in the ParameterBox Remedy 12.0 External watchdog The Watchdog function is selected at a digital input and the impulse at the corresponding digital input is not present for longer than the time set in parameter P460 >Watchdog time<. 12.1 Motor limit "Motor switch-off limit" The drive switch-off limit (P534 [-01]) has triggered. Group Details in P700[-01] / P701 E012 Reduce load on motor Set higher value in (P534 [-01]). 12.
SK 180E Manual for frequency inverters Display in the SimpleBox Fault Cause Text in the ParameterBox Remedy Group Details in P700[-01] / P701 E015 15.0 Reserved E016 16.0 Motor phase error A motor phase is not connected. Check P539 Check motor connection 16.1 Magn. current monitoring "Magnetisation current monitoring" Required exciting current not achieved at moment of switch-on. Check P539 Check motor connection Reserved E018 E019 19.0 Parameter ident.
7 Status messages 7.2.2 Table of possible error messages in the I/O extension module Error number Fault Cause Group Text in the ParameterBox Remedy EEPROM error EMC interference on the SPI bus Details in P170 E1000 1000 Module faulty 1030 System bus OFF Check connections and supply cables Ensure 24 V voltage supply Check bus master. E2000 2000 2001 DIP changed DIP switch configuration changed during operation DIP configuration incorrect Illegal DIP switch setting Check DIP switch setting.
SK 180E Manual for frequency inverters 7.3 Table of possible warning messages Display Group Details in P700 [-02] C001 1.0 Warning Cause Text in the ParameterBox Remedy Overtemp. inverter “Inverter overtemperature“ (inverter heat sink) Warning from output stage module (static) Reduce ambient temperature <50°C or <40°C (see also Section 8 Technical data) Check ventilation C002 2.0 Overtemp.
7 Status messages Display Warning Cause Group Details in P700 [-02] Text in the ParameterBox Remedy C008 8.0 Parameter loss Warning: One of the cyclically saved messages such as operating hours or enabling time could not be saved successfully. The warning disappears as soon as saving can be successfully performed. C012 12.1 Motor limit "Motor switch-off limit" Warning: 80% of the drive torque switch-off limit (P534 [-01]) has been exceeded.
SK 180E Manual for frequency inverters 7.4 Table of possible reasons for the operating status "switch-on disabled" The following table summarises the messages which are generated if the frequency inverter cannot be enabled, although no fault is present. Display Reason: Cause Group Details in P700 [-03] Text in the ParameterBox Remedy I000 0.
8 Technical data 8 Technical data 8.1 General data for frequency inverter series SK 1x0E Function Specification Output frequency 0.0 … 400.0 Hz Pulse frequency 3.0 … 16.0 kHz, standard setting = 6 kHz Power reduction > 8 kHz for 115/230V device, >6 kHz for 400 V device. Typical overload capacity 150% for 60 s, 200% for 3.
SK 180E Manual for frequency inverters 8.2 Electrical data for frequency inverter The following table lists the electrical data for SK1x0E series frequency inverters. The details based on measurement series for the operating modes are for orientation purposes and may deviate in practice.
8 Technical data 8.2.1 Electrical data 1~115V Size 1 Device type: SK 1x0E… -370-112-O -550-112-O -750-112-O 0.25 kW 0.37 kW 0.55 kW 0.75 kW ½ hp ¾ hp 1 hp 230 V Nominal motor power (4-pole standard motor) 1 240 V 1 AC 110 … 120 V, 10%, 47 … 63 Hz 1~ rms 9.1 A 11 A 14.3 A 18 A 1~ FLA 9.1 A 11 A 14.3 A 18 A 1 AC slow-acting [A] 16 A 16 A 16 A 25 A RK5 or faster fuses, min.
SK 180E Manual for frequency inverters 8.2.2 Electrical data 1/3~230V Size 1 SK 1x0E… Device type: Nominal motor power 230 V (4-pole standard motor) 240 V -370-323-B -550-323-B 0.25 kW 0.37 kW 0.55 kW ½ hp ¾ hp 1 /3 hp 1/3 AC 200 ... 240V, 10%, 47 ... 63 Hz 1~ /3~ 230 V Mains voltage Typical input current at 230V Input Rec. mains fuse Permissible mains fuses (UL) 1~ / 3~ rms 4.5 A / 3.2 A 5.7 A / 3.8 A 7.2 A / 4.8 A 1~ / 3~ FLA 4.5 A / 3.2 A 5.7 A / 3.8 A 7.2 A / 4.
8 Technical data Size 2 SK 1x0E… Device type: -750-323-B -111-323-B -151-323-B Nominal motor power 230 V 0.75 kW 1.1 kW 1.5 kW (4-pole standard motor) 240 V 1 hp 1½ hp 2 hp 1/3 AC 1~ /3~ 230 V Mains voltage Input 200 ... 240V, 10%, 47 ... 63 Hz 1~ / 3~ rms 10.6 A / 7 A 14 A / 9.2 A - / 11.2 A 1~ / 3~ FLA 10.6 A / 7 A 14 A / 9.2 A - / 11.2 A 16 A 16 A 16 A RK5 or faster fuses, min 230 V 30 A / 10A 30 A 30 A Bussmann FRS-R-30 FRS-R-30 FRS-R-30 Circuit breaker* min.
SK 180E Manual for frequency inverters 8.2.3 Electrical data 3~400 V Size 1 SK 1x0E… Device type: 400 V Nominal motor power (4-pole standard motor) -550-340-B -750-340-B -111-340-B 0.25 kW 0.37 KW 0.55 kW 0.75 kW 1.1 kW ½ hp ¾ hp 1 hp 1½ hp 1 3 AC 380 ... 480V, -20% / +10%, 47 ... 63 Hz 3~ rms 2.0 A 2.3 A 2.6 A 3.2 A 4.1 A 3~ FLA 1.7 A 1.9 A 2.2 A 2.7 A 3.5 A 1 AC slow-acting [A] 10 A 10 A 10 A 10 A 10 A RK5 or faster fuses, min 230V/400 V 5.0 A 5.0 A 5.0 A 5.
8 Technical data Size 2 SK 1x0E… Device type: -151-340-B -221-340-B Nominal motor power 400 V 1.5 kW 2.2 kW (4-pole standard motor) 480 V 2 hp 3 hp 3~ 400 V 3 AC 380 ... 480V, -20% / +10%, 47 ... 63 Hz Mains voltage 3~ rms 6A 7A 3~ FLA 5A 5.9 A 1 AC slow-acting [A] 10 A 10 A RK5 or faster fuses, min 230V/400 V 10 A 10 A FRS-R-10 FRS-R-10 10 A 10 A Typical input current at 400V Input Rec. mains fuse Permissible mains fuses (UL) Bussmann Circuit breaker* min.
SK 180E Manual for frequency inverters 9 Additional information 9.
9 Additional Information 9.2 Process controller The process controller is a PI controller which can be used to limit the controller output. In addition, the output is scaled as a percentage of a master setpoint. This provides the option of controlling any downstream drives with the master setpoint and readjusting using the PI controller. Ramp time PI setpoint P416 Master setpoint a) Analog input 1 (P400[-01]=2) b) or c) Analog input 2 Min. limit P466 Setpoint a) P412 = 0.0-10.
SK 180E Manual for frequency inverters 9.2.2 Process controller parameter settings (Example: Setpoint frequency: 50 Hz, control limits: +/- 25%) P105 (maximum frequency) [Hz] : Setpointfrq.Hz P 415% Setpointfrq.Hz 100% Example: 50 Hz 50 Hz 25% 62.5 Hz 100% P400 [-01] (Funct.
9 Additional Information 9.3 Electromagnetic compatibility (EMC) 9.3.1 General Provisions As of July 2007, all electrical equipment which has an intrinsic, independent function and which is sold as an individual unit for end users, must comply with Directive 2004/108/EEC (formerly Directive EEC/89/336). There are three different ways for manufacturers to display compliance with this directive: 1.
SK 180E Manual for frequency inverters The essential correlation between the two standards is illustrated as follows: Category according to product standard EN 61800-3 Limit value class according to EN 55011 Operation permissible in 1st environment (domestic environment) 2nd environment (industrial environment) Information required according to EN 61800-3 Distribution method EMC knowledge C1 C2 C3 B A1 A2 X X - X X 1) X 2) Generally available No requirements Limited availability Installation and
9 Additional Information Overview of the standards, which according to product standard EN 61800-3 are applicable as testing and measuring methods for electric drives whose speed can be altered: Emission of interference C1 (only if mounted on motor) Emission from cables (interference voltage) EN 55011 Radiated emissions (Interference field strength) EN 55011 Interference immunity otherwise C2 C1 (only if mounted on motor) otherwise C2 EN 61000-6-1, EN 61000-6-2 ESD, discharge of static electricity
SK 180E Manual for frequency inverters 9.3.
9 Additional Information 9.4 Reduced output power The frequency inverter is designed for certain overload situations. For example, 1.5x overcurrent can be used for 60 sec. For approx. 3.5 sec a 2x overcurrent is possible.
SK 180E Manual for frequency inverters 9.4.2 Reduced overcurrent due to time The possible overload capacity changes depending on the duration of an overload. Several values are cited in this table. If one of these limiting values is reached, the frequency inverter must have sufficient time (with low utilisation or without load) in order to regenerate itself. If operated repeatedly in the overload region at short intervals, the limiting values stated in the tables are reduced.
9 Additional Information 9.4.3 Reduced overcurrent due to output frequency To protect the power unit at low output frequencies (<4.5 Hz) a monitoring system is provided, with which the temperature of the IGBTs (integrated gate bipolar transistor) due to high current is determined. In order to prevent current being taken off above the limit shown in the diagram, a pulse switch-off (P537) with a variable limit is introduced. At a standstill, with 6 kHz pulse frequency, current above 1.
SK 180E Manual for frequency inverters 9.4.4 Reduced output current due to mains voltage The devices are designed with thermal characteristics according to the nominal output currents. Accordingly, for lower mains voltages, higher currents cannot be taken off in order to maintain the stated power constant.
9 Additional Information 9.5 Operation with FI circuit breakers With frequency inverters (except 115V devices), leakage currents of up to 16mA are to be expected if the mains filter is active. These are designed for operation with leakage current circuit breakers for the protection of persons. For further details, please refer to Section 2.7.4. 9.6 System bus Frequency inverters and components communicate with each other via the system bus. This bus system is a CAN bus with CANopen protocol.
SK 180E Manual for frequency inverters Addressing If several frequency inverters are connected to a system bus, these devices must be assigned with unique addresses. This is preferably implemented via DIP switch S2 of the frequency inverter (Section 5.2.2.2). Frequency inverters FI 1 FI 2 FI 3 FI 4 Addressing via DIP switch S2 DIP2 DIP1 ON ON ON OFF OFF ON OFF OFF Resulting Node ID Frequency inverters 32 34 36 38 For field bus modules, no assignment of addresses is necessary.
9 Additional Information 9.7 Energy Efficiency NORD frequency inverters have a low power consumption and are therefore highly efficient. In addition, with the aid of "Automatic flux optimisation" (Parameter (P219)) the inverter provides a possibility for increasing the overall efficiency of the drive in certain applications (in particular applications with partial load).
SK 180E Manual for frequency inverters 9.8 Motor data - characteristic curves 9.8.1 50Hz characteristic curve ( Variation 1:10) a) 115V / 230 V frequency inverter The motor used for 50 Hz operation can be operated up to its rated point 50 Hz/230 V with the nominal torque. In spite of this, operation above 50Hz is possible, however the output torque reduces in a non-linear manner (see following diagram).
9 Additional Information b) 400 V frequency inverter The motor used for 50 Hz operation can be operated up to its rated point 50 Hz/400 V with the nominal torque. In spite of this, operation above 50 Hz is possible, however the output torque reduces in a non-linear manner (see following diagram). Above the rated point, the motor enters its field weakening range, as the voltage cannot be raised over 400 V when the frequency is increased above 50 Hz. Because of the mains voltage, maximum 400 V are available.
SK 180E Manual for frequency inverters 9.8.2 87Hz characteristic curve (only 400 V devices) ( Variation 01:17:00) The 87 Hz characteristic represents an extension of the speed adjustment range with a constant motor nominal torque.
9 Additional Information 9.8.3 100Hz characteristic curve (only 400 V devices) ( Variation 01:20:00) An operating point 100 Hz/400 V can be selected for a greater speed adjustment range with up to a ratio of 1:20. Special motor data are required (see below) that differ from the normal 50 Hz data. It must be ensured in this case that a constant torque is generated across the entire adjustment range but that it is smaller than the nominal torque for 50 Hz operation.
SK 180E Manual for frequency inverters 9.9 Standardisation of setpoint / target values The following table contains details for the standardisation of typical setpoint and actual values. These details relate to parameters (P400), (P418), (P543), (P546), (P740) or (P741).
9 Additional Information 9.10 Definition of setpoint and actual value processing (frequencies) Function The frequencies used in parameters (P502) and (P543) are processed in various ways according the following table. 1 2 3 Setpoint source and setpoint selection Signal processing and ramp Control and motor model (determination of slip) Output to ...
SK 180E Manual for frequency inverters 9.11 Maintenance and servicing information 9.11.1 Maintenance Instructions In normal use, frequency inverters are maintenance-free. Please note the "General data" in Section 8.1. Dusty environments If the frequency converter is being used in a dusty environment, the cooling-vane surfaces should be regularly cleaned with compressed air. If air intake filters have been built into the control cabinet, then these should also be regularly cleaned or replaced.
9 Additional Information 9.11.2 Repair information If you contact our technical support, please have the precise device type (rating plate/display), accessories and/or options, the software version used (P707) and the series number (name plate) at hand. Repairs The device must be sent to the following address if it needs repairing: NORD Electronic DRIVESYSTEMS GmbH Tjüchkampstraße 37 26605 Aurich, Germany For queries about repairs, please contact: Getriebebau NORD GmbH & Co. KG Tel.
SK 180E Manual for frequency inverters 9.12 Abbreviations in this manual 180 AS (AS1) AS interface FI .......... Frequency inverter AIN ....... Analog input ISD ........ Field current (Current vector control) AOUT ... Analog output LED....... Light-emitting diode BW ....... Brake resistor S .......... Supervisor Parameter, P003 DI (DIN) Digital input S1 ......... DIP switch FI A-IN (3-pole) DO (DOUT) Digital output S2 ......... DIP switch FI (3-pole) I/O ......... Input / Output SW ...
9 Additional Information 10 Keyword index 3 3-Wire-Control .......................... 102 A Absolute minimum frequency (P505) .................................. 111 Acceleration time (P102) ........... 81 Accessories .................................. 9 Actual cos phi (P725) ...................... 130 Frequency (P716)................. 130 Mains current (P760) ............ 135 Setpoint frequency (P718) .... 130 Speed (P717) ....................... 130 Voltage (P176) .....................
SK 180E Manual for frequency inverters F Factor display (P002) .................. 80 Factory setting ............................ 65 Factory setting (P523)............... 115 Factory settings (P152) ............. 136 Faults .......................... 63, 140, 141 Features ........................................9 FI circuit breaker ................. 11, 169 Field (P730) .............................. 131 Filter time (P161) ...................... 137 Fixed frequency array (P465)....
10 Key word index Process controller control limit (P415) .................................... 98 Process controller setpoint (P412) ............................................... 98 Process data Bus In (P740) ..... 132 Process data Bus Out (P741)... 133 Protection class .......................... 20 Pulse disconnection (P537)...... 120 Pulse frequency (P504) ............ 111 Q Queries..................................... 179 Quick stop time (P426) ............. 103 R Ramp rounding (P106) ..............
Part No.