5 Parameterisation 
BU 0135 GB-2713  Pre-series version  73 
Parameter 
{ Factory setting } 
Setting value / Description / Note 
READ  RAM 
READ / 
FLASH 
FLASH 
P709  [-01]
  ...
  [-04]
Potentiomet. status 
(Potentiometer status)  
x       
0.0 ... 100.0 %  Displays the measured analog input value at the potentiometers. 
[-01] =  Potentiometer 1 
[-02] =  Potentiometer 2 
[-03] =  Potentiometer 3 
[-04] =  Potentiometer 4 
P711 
Digital output status  
(Status of digital output) 
x       
0000 ... 0111 (bin) 
or 
00 ... 07 
(hex) 
Indicates the actual status of the digital outputs of the motor starter. 
Bit 0 = Digital output 1 
Bit 1 = Digital output 2 
Bit 2 = mechanical brake  
  Bits 3-0   
Minimum value 
0000 
0 
Binary 
hex 
Maximum value 
0111 
7 
Binary 
hex 
SimpleBox: The binary Bits are converted into a hexadecimal value and displayed. 
ParameterBox:   The Bits are displayed with increasing values from right to left (binary). 
P716 
Actual frequency 
(Actual frequency)  
x       
-70.0 ... 70.0 Hz 
Displays the actual output frequency. This is calculated from the mains frequency and the 
selected direction of rotation on enabling. "0" is output when the device is switched off. 
P718   
Mains frequency 
(Mains frequency)  
x       
-70.0 ... 70.0 Hz  Displays the mains frequency determined by the motor starter. 
P719 
Actual current 
(Actual current)  
x       
0.0 ... 999.9 A  Displays the actual output current. 
P720 
Effective current 
(Actual effective current) 
x       
-999.9 ... 999.9 A  Displays the actually measured effective current.  
à negative values = generator, à positive values = drive 
P721 
Reactive current 
(Actual reactive current)  
x       
-999.9 ... 999.9 A  Displays the actually measured reactive current.  
P722 
Current voltage 
(Actual voltage)  
x       
0 ... 500 V  Displays the actual AC voltage supplied by the motor starter output. 
P723 
Voltage -d  
(Actual voltage component Ud)  
S       
0 ... 500 V  Usually this value is "0" 