User guide

5 Parameterisation
BU 0135 GB-2713 Pre-series version 67
5.1.4 Control terminals
Parameter
{ Factory setting }
Setting value / Description / Note
READ RAM
READ /
FLASH
FLASH
P400 [-01]
[-04]
Fnct. Potentiometer
(Potentiometer function)
x
0 ... 6
{ [-01] = 1 }
Rated current of
motor
{ [-02] = 2, 5
11
}
Locking time
Acceleration time
{ [-03] = 3 }
Starting torque
{ [-04] = 4, 6
12
}
Ramp time
Deceleration time
Here the set functions for up to four potentiometers can be viewed.
It is not possible to change
the setting.
0 = No function, the potentiometer is not used
1 = Rated motor current, value for P203 as long as P130=0
2 = Locking time, value for P570 as long as P130=0
3 = Starting torque, value for P210 as long as P130=0
4 = Ramp times, value for P102 and P103 as long as P130=0
5 = Acceleration time, value for P102 as long as P130=0
6 = deceleration time, value for P103 as long as P130=0
P420 [-01]
[-07]
Digital inputs
(digital input functions)
x
0 ... 9
{ [-01] = 1 } Digital
input 1
{ [-02] = 2 } Digital
input 2
{ [-03] = 8 }
13
Thermistor
{ [-04] = 3 }
Bus In Bit 0
{ [-05] = 4 }
Bus In Bit 1
{ [-06] = 7 }
Bus In Bit 2
{ [-07] = 9 }
Bus In Bit 3
Here the set functions for up to seven digital inputs can be viewed. It is possible to change the
setting if parameter P130=1 is set. Otherwise the value can only be views and is fixed.
0 = No function
1 = Enable right (only possible for digital input 1 and 2)
2 = Enable left (only possible for digital input 1 and 2)
3 = Enable right via bus (only possible for digital inputs 4 to 7)
4 = Enable left via bus (only possible for digital inputs 4 to 7)
5 = Block voltage
6 = Quick stop
7 = Error acknowledgement
8 = PTC resistor input
9 = Release the brake
P427
Emerg. stop Error
(Emergency stop on error)
x
0 ... 1
{ 0}
I
n case of errors E2.0, E3.0, E5.1 and E6.1 there is the option that the drive is not switched off
immediately if the error occurs, but rather with devices with a soft start function, these are run
down the ramp as normal before switch-off.
0 = Disabled: Automatic quick stop following error is deactivated
1 = Activated: Automatic quick stop following error is activated
11
Acceleration time for type SK 115E and SK 155E devices (5) Locking time for all other devices (2)
12
Deceleration time for type SK 115E and SK 155E devices (6) Ramp time for all other devices (4)
13
The thermistor input cannot be re-programmed to another function.