User guide
5 Parameterisation 
BU 0135 GB-2713  Pre-series version  63 
5.1.2  Basic parameters 
Parameter 
{ Factory setting } 
Setting value / Description / Note 
READ  RAM 
READ / 
FLASH 
FLASH 
P102 
Acceleration time  
(Acceleration time)
    x   
0 ... 25.50s 
{ 1.00 / P4} 
For devices wit
h integrated soft start function, the time is set here, with which the phase control 
is increased from the starting angle to full control. Therefore, the acceleration time only 
indirectly determines the actual time that the motor accelerates. The resulting acceleration time 
of the motor essentially depends on the motor which is used, the inertial masses and the 
counter-torque.  
NOTE: 
As long as P130=0 is set, P102 is determined via potentiometer P4. In this case, the 
parameter can only be read and not chang
ed and corresponds to the value which is set by the 
potentiometer.  
P103 
Deceleration time  
(deceleration time) 
    x   
0 ... 25.50s 
{ 1.00 / P4} 
For devices with integrated soft start function, the time is set here, with 
which the phase control 
is reduced, starting from full control or the starting control down to the minimum phase control. 
Therefore, the deceleration time only indirectly determines the actual time that the motor 
decelerates. The resulting deceleration tim
e of the motor essentially depends on the motor 
which is used, the inertial masses and the counter-torque.  
NOTE: 
As long as P130=0 is set, P103 is determined via potentiometer P4. In this case, the 
parameter can only be read and not changed and correspond
s to the value which is set by the 
potentiometer.  
P107 
Brake reaction time  
(Brake reaction time) 
    x   
0 ... 25.50s 
{ 0.00 / P4 } 
This parameter determines the time after which the brake is applied after the starter has 
blocked its voltage at the output. This enables the motor to reduce its speed or even stop before 
the brake is applied. If P114=0, the value which is set here also applies for the release time 
(P114) 
NOTE: 
For lifting gear applications, with brakes whic
h are applied very slowly, a slight sagging of the 
load cannot be prevented, as the motor usually switches off before the brake is applied 