User guide
5 Parameterisation 
BU 0135 GB-2713  Pre-series version  61 
5.1  Parameter 
All parameters can be adjusted "online" 
NOTE 
After parameterisation, initially only the value in the RAM is changed. In order to make the 
parameterisation permanent, the parameters must be transfer
red from the RAM to the flash 
memory (see parameter P550). 
In the state as delivered, the characteristics /parameter settings of the motor starter are 
essentially determined by DIP switch S and up to four potentiometers. If all of the settings are to 
be made via parameters, parameter P130 must be set accordingly. 
The individual parameters are combined in various groups. The first digit of the parameter number indicates 
the assignment to a menu group: 
Menu group   No.  Master function 
Operating displays   (P0--): 
For the selection of the physical units of the display value. 
Basic parameters   (P1--): 
Contain basic motor starter settings, e.g. switch on and switch off procedures 
and, along with the motor data, are sufficient for standard applications. 
Motor data    (P2--): 
Setting of the motor current and starting torque / starting voltage for motor 
starters with integrated soft start. 
Control terminals   (P4--): 
Analog input and output scaling, specification of digital input and relay output 
functions. 
Additional parameters   (P5--): 
Functions dealing with e.g. the BUS interface, pulse frequency or error 
acknowledgement. 
Information     (P7--): 
Display of e.g. actual operating values, old error messages, equipment status 
reports or software version. 
Array parameters  -01 
      ... 
      -xx 
Some parameters in these groups can be programmed and read in several levels 
(arrays). After the parameter is selected, the array level must also be selected. 
Note 
Parameter P523 ca
n be used to load the factory settings for all parameters at any time. This can 
be helpful, e.g. during the commissioning of a motor starter whose parameters no longer 
correspond with the factory settings.  
Note 
If parameter changes are to be permanen
tly saved in the motor starter, they must be copied 
from the RAM to the flash memory using parameter P550. This copying process can only be 
guaranteed for approx. 100 times. 
Note / Explanation: 
Feature  Meaning 
READ  Parameter can only be read 
RAM  Parameter can be changed, but cannot be saved in the flash memory. 
READ / 
FLASH 
According to the setting of parameter P130, the parameter can either only be read or 
can be changed and saved in the flash memory. 
FLASH  The parameter is read out of the flash memory and can be changed. 