User guide
4 Commissioning 
BU 0135 GB-2713  Pre-series version  47 
4.2.2.2  DIP switches 
Individual functions of the motor starters can be set by means of a quadruple DIP switch. These differ ac-
cording to the equipment version. 
DIP 
switches 
Functionality  Functionality  105E
145E 
115E
155E 
125E
165E 
135E
175E 
DIP1 
Automatic start 
0: Enable with flank   
1: Enable with level 
+  +  +  + 
DIP2 
Phase sequence 
detection 
0: According to phase sequence 
 Mains connection 
1: According to phase sequence  
 Required direction of rotation 
à
Automatic detection of   
 phase sequence 
+  + 
DIP2 
Switch off with error in 
case of 
overtemperature 
0: Starter switches off on 
 overtemperature 
1: No switch off on  
 overtemperature 
à
only warning  
+ 
  * 
DIP3 
Release the brake 
0: Brake released on 
 enable 
1: Brake is permanently  
 released 
+ 
+ 
DIP4 
Switch off with error in 
case of 
overtemperature 
0: Starter switches off on 
 overtemperature 
1: No switch off on  
 overtemperature 
à
only warning  
+ 
+ 
* 
DIP3, 4 
Switch-off ramp 
00: Deceleration mode 1 
01: Deceleration mode 2 
10: Deceleration mode 3 
11: Deceleration mode 4 
+ 
+ 
* For SK 135E and SK 175E devices the function "Switch off with error on overtemperature" can only be ena-
bled via parameter P580. 
4 3 2 1 
ON 
OFF 