Datasheet
Data sheet for General Purpose Toroidal Transformers – 160VA Economy Series
Dual Primary winding for connection in series or
parallel only.
Input voltage : 115V or 230V +/-10% 50/60 Hz
Dc resistance : 2 x 5 Ohms +/-20% @ 20
o
C
Magnetising current : 11,5mA @ primary 230V 50Hz
23mA @ primary 115V 50Hz
All leads UL1569 / UL1015 / 105
o
C
Primary leads Double insulated with Insulation Class B
tubes, minimum length 20mm
Lead length Tolerance +/-10mm
all lead ends 6mm tinned
All Leads exit at the outer top edge,
Iron loss : 1,36 Watts
Copper loss : 13,56Watts
Efficiency : 91% Typical
Calculated Temperature rise : 50
o
C
( In open environment )
Maximum rated ambient : 40
o
C
Winding wire : Class H (180
o
C)
Insulation System : Class B (130
o
C)
Leads insulation : Class A (105
o
C)
Degrees of protection : IP00
!"
Diameter : 105mm
Inner Diameter : 34mm
Height : 45mm
Weight : 1,75kg
#$
1 x Metal washer 90mm
2 x Rubber pad 90mm
1 x M6 Screw, nut and washer
%%
Designed and manufactured in accordance with : EN61558-1 / EN61558-1/A1 / EN61558-2-4 or EN61558-2-6
UL recognised under family approval E115159 and E20244 to UL1411,UL60601-1,UL1950.
#&
Model number xxxxxxxx ta40/A IP00
Prim. 2 x 115V 50Hz Fuse XXAT
Thermal fuse 125
o
C E115159
Sec. 2 x rated voltage and rated current Amp FuseXXAT Z125
Art. No. ES0160/XX
Ordering Code
Art. No.
Load
voltage
No load
voltage
Rated
current
Secondary
wire gauge
Sec. DC resistance
Ohoms @ 20
o
C
+/-20%
TI-044226-ME-ES ES0160/12 2 x 12V 2 x 13V 2 x 6,67A
AWG14 2 x 0,12
TI-044227-ME-ES ES0160/15 2 x 15V 2 x 16,2V 2 x 5,33A
AWG16 2 x 0,11
TI-044228-ME-ES ES0160/18 2 x 18V 2 x 19,5V 2 x 4,44A
AWG16 2 x 0,16
TI-044229-ME-ES ES0160/25 2 x 25V 2 x 27,1V 2 x 3,2A AWG18 2 x 0,31
TI-044230-ME-ES ES0160/30 2 x 30V 2 x 32,5V 2 x 2,67A
AWG18 2 x 0,46
TI-044231-ME-ES ES0160/55 2 x 55V 2 x 59,6V 2 x 1,45A
AWG20 2 x 1,51
OR
Sec V (80VA)
Sec V (80VA)
115V
0V
0V
115V
0V
0V
Primary
Secondary
Thermal fuse 125
o
C
Thermal fuse 125
o
C
%' ()
$&' ()
*' ()
$' ()
+$$*
)
,$
(