Manual

5-47
Alarm OR, special OFF setup, and delay time unit
Alarm OR, special OFF setup, and delay time unit accompanying with the
operation type can be set.
• When the internal event configuration 1 operation type is set at [0: No event], the
internal event configuration 3 (alarm OR, special OFF setup, and delay time unit)
is not displayed.
The following shows the relationship among alarm OR setting, alarm present/not
present, and internal event ON/OFF:
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Item (Setting display/bank) Display Contents Initial value User level
Internal Event 1
Configuration 3 Operation
type
(Setup setting/Event
Configuration bank)
The digits are called 1st digit, 2nd digit, 3rd
digit, and 4th digit from the right end.
1st digit: Alarm OR setup
0: None
1: Alarm direct + OR operation
2: Alarm direct + AND operation
3: Alarm reverse + OR operation
4: Alarm reverse + AND operation
2nd digit: Special OFF setup
0: As usual.
1: When EV main setting is “0”, the
event is set to “OFF”.
3rd digit: Delay time unit setup
0: 0.1s
1: 1s
2: 1 min.
4th digit: Undefined.
0: Undefined.
0000
High function
0000
Internal Event 2
Configuration 3 Operation
type
(Setup setting/Event
Configuration bank)
0000
Internal Event 3
Configuration 3 Operation
type
(Setup setting/Event
Configuration bank)
0000
Internal Event 4
Configuration 3 Operation
type
(Setup setting/Event
Configuration bank)
0000
Internal Event 5
Configuration 3 Operation
type
(Setup setting/Event
Configuration bank)
None Not present OFF OFF
Not present ON ON
Present. OFF OFF
Present. ON ON
Alarm direct + Not present OFF OFF
OR operation Not present ON ON
Present. OFF ON
Present. ON ON
Alarm direct + Not present OFF OFF
AND operation Not present ON OFF
Present. OFF OFF
Present. ON ON
Alarm reverse + Not present OFF ON
OR operation Not present ON ON
Present. OFF OFF
Present. ON ON
Alarm reverse + Not present OFF OFF
AND operation Not present ON ON
Present. OFF OFF
Present. ON OFF
Alarm OR setting
Alarm (AL01 to
99) present/not
present
Internal event
ON/OFF status before
alarm OR process
Internal event
ON/OFF status after
alarm OR process