Manual

13-4
Chapter 13. SPECIFICATIONS
Isolation between input and output
Portions enclosed by solid lines are insulated from other signals.
Whether or not inputs and outputs are provided may vary depending on the model.
In case of the independent contacts, the output 1 and the output 2 are isolated.
Environment conditions
• Standard conditions
Ambient temperature: 23±2˚C
Ambient humidity: 60±5%RH
Power supply voltage: AC power model, 105Vac±1%, 50/60Hz±1Hz
DC power model, 24Vac±1%, 50/60Hz±1Hz
24Vdc±5%
Vibration: 0m/s
2
Shock: 0m/s
2
Mounting angle: (Reference plane) ±3˚
• Operating conditions
Ambient temperature: 0 to 50˚C (0 to 40˚C for tight-mounting)
Ambient humidity: 10 to 90%RH (No condensation allowed.)
Power supply voltage: AC power model, 85 to 264Vac, 50/60Hz±2Hz
(Rating: 100 to 240Vac, 50/60Hz)
DC power model, 21.6 to 26AVac, 50/60Hz±2Hz/21.6 to 52.8Vdc
(Rating: 24Vac, 50/60Hz 24 to 48Vdc)
Vibration: 0 to 2m/s
2
(10 to 60Hz for 2 hrs. in each of the X-, Y-, and Z-direction)
Shock: 0 to 10m/s
2
Mounting angle: (Reference plane) ±10˚
• Transportation conditions
Ambient temperature: -20 to +70˚C
Ambient humidity: 10 to 95%RH (No condensation allowed.)
Power supply Control output 1
PV input Control output 2
CT input 1 Internal circuit
CT input 2 Event output 1
Loader communication Event output 2
Digital input 1 Event output 3
Digital input 2
RS-485 communication