Manual
Chapter 13. SPECIFICATIONS
13-1
■ Specifications
● PV input
Input type: Thermocouple K, J, E, T, R, S, B, N (JIS C1602-1995)
PL II (Engelhard Industries data(ITS90))
WRe5-26 (ASTM E988-96(Reapproved 2002))
DIN U, DIN L (DIN43710-1985)
RTD Pt100 (JIS C1604-1997), JPt100 (JIS C1604-1989)
DC voltage 0 to 1Vdc, 1 to 5Vdc, 0 to 5Vdc, 0 to 10Vdc
DC current 0 to 20mAdc, 4 to 20mAdc
Sampling cycle time: 500ms
Indication accuracy: ±0.5%FS±1 digit, ±1%FS±1digit in the negative area of the thermocouple
(Specified by the input conversion at an ambient temperature of 23±2˚C)
However, the accuracy of the B-thermocouple is ±5%FS at a temperature
of 260˚C or less and ±1%FS at a temperature of 260 to 800˚C.
The low limit for indication is 20˚C. However, if ROM version 1 of the
instrument information bank (Id02) is prior to 2.04, the low limit for
indication is -180˚C.
PV bias: -1999 to +9999 or -199.9 to +999.9
• Thermocouple (T/C) input
Input bias current: +0.2µA (Flowed from the A terminal.)
Burnout indication: Upscale + AL01
Thermocouple or
compensating wire: 0.3 to 0.65mm diameter
• Resistance temperature detector (RTD) input
Input bias current: Approx. +1mA (Flowed from the A terminal.)
Burnout indication: RTD burnout or A-wire burnout
. . . . .
Upscale + AL01
B-wire burnout or C-wire burnout
. . . .
Upscale + AL01, AL03
2 or more wires burnout
. . . . . . . . . . . .
Upscale + AL01, AL03
Allowable wiring
resistance: Max. 10Ω at range No.51 to 64, max. 85Ω the other ranges.
Influence of wiring
resistance: Max. ±0.05% FS/Ω Max. 10Ω at range No.51 to 64, max. 85Ω the other
ranges.
• DC voltage input
Input impedance: Min. 1MΩ
Input bias current: 0 to 1V range
. . . . . . . . . . . . . . . . . . . .
1µA (sucked to the A terminal)
0 to 5V, 1 to 5V range
. . . . . . . . . . . . .
3.5µA (sucked to the A terminal)
0 to 10V range
. . . . . . . . . . . . . . . . . . .
7µA (sucked to the A terminal)
Burnout indication: Downscale + AL02
However, the burnout cannot be detected in a range of 0 to 10V.
• DC current input
Input impedance: Max. 100Ω
Burnout indication: Downscale + AL02
However, the burnout cannot be detected in a range of 0 to 20mA.
Allowable input
current: Max. 30mA