Manual

11-3
• The PV input type is T (thermocouple).
• The PV input type is R (RTD).
• The PV input type is L (DC voltage/DC current).
(5) Keep the apply status for approximately 30 sec.
(6) Click [Write].
(7) Return to step (2) until the final gain No. is completed.
Handling Precautions
In the PV input calibration, always adjust all gains.
Do not leave the PV input terminal open during heat-up between
power ON of this unit and starting of calibration. When the input type
is thermocouple or DC voltage, put the unit in the 0V-input (or
terminals are short-circuited) status. When the input type is RTD, put
the unit in the 100-input (or terminals are short-circuited) status.
Chapter 11. CALIBRATION
Voltage
generator
This unit
-
+
(4)
(5)
(6)
Resistor
This unit
(4)
(5)
(6)
Voltage
generator
Gain Nos. 1 to 12 (voltage)
This unit
-
+
(4)
(5)
(6)
Current
generator
Gain Nos. 13 to 16 (current)
This unit
-
+
(4)
(5)
(6)