Manual

1 - 2 Part Names and Functions
1-4
Main body and console
Main body: Contains the electric circuit for I/O signals of measuring instruments,
CPU, and memory.
Console: Contains the display panel showing numeric value and status, and
operation keys.
Detailed description of console
[mode] key
When this key is kept pressed for 1 sec. or longer in the operation display
mode, any of the following operations, which have been set previously, can be
performed:
AUTO/MANUAL mode selection
RUN/READY mode selection
AT (Auto Tuning) start/stop selection
LSP (Local SP) group selection
Release all DO (Digital Output) latches
ON/OFF selection of communication DI (Digital Input) 1
When pressing the [mode] key in the setup display mode, the display is
changed to the operation display.
[para] key
This key is used to change the display item.
When this key is kept pressed for 2 sec. or longer in the operation display
mode, the display is then changed to the setup display.
[<], [], []keys
These keys are used to increase or decrease the numeric value, or to shift the
digit.
<
<
Chapter 1. OVERVIEW
ot2
ot1
ev3
ev2
ev1
man
rdy
para
mode
Main bodyConsole
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
Lower Display
Mode indicator
[<], [ ], and [ ] keys
<
<
[para] key
Upper display
[mode] key
Console