Manual

Chapter 10. MAINTENANCE AND
TROUBLESHOOTING
10-1
Maintenance
Cleaning
When removing the dirt from the measuring instrument, wipe it off with a soft
cloth rag. At this time, do not use any organic solvent, such as paint thinner or
benzene.
Part replacement
Do not replace any parts of this unit.
Fuse replacement
When replacing the fuse connected to the electric wiring, always use the specified
standard fuse.
Standard IEC127
Shut-down speed Slow-action type (T)
Rated voltage 250V
Rated current 200mA
Alarm displays and corrective action
The following Table shows the alarm displays and corrective actions if any failure
occurs in this unit:
Alarm code
Failure name Cause Corrective action
PV input failure Sensor burnout, incorrect wiring,
(Over-range) incorrect PV input type setting
PV input failure Sensor burnout, incorrect wiring,
(Under-range) incorrect PV input type setting
CJ failure Terminal temperature is faulty
(thermocouple).
PV input failure Sensor burnout, incorrect wiring Check the wiring.
(RTD)
CT input failure A current exceeding the upper
(over-range) limit of the display range was
(CT input 1 or 2, measured. The number of CT
or both) turns or the number of CT
power wire loops is incorrectly
set, or wiring is incorrect.
A/D conversion A/D converter is faulty.
failure
Parameter failure Data is corrupted by noise, or
power is shut-down while the
data is being set.
Adjustment data Data is corrupted by noise, or
failure power is shut-down while the
data is being set.
Parameter failure Data is corrupted by noise.
(RAM area)
Adjustment data Data is corrupted by noise.
failure (RAM area)
ROM failure ROM (memory) is faulty.
Check the wiring.
Set the PV input type
again.
Check the ambient
temperature.
Replace the unit.
• Restart the unit.
• Set the data again (set
data for AL95/97 and
adjustment data for
AL96/98).
• Replace the unit.
• Restart the unit.
• Replace the unit.
• Use a CT with the correct
number of turns for the
display range.
• Reset the number of CT
turns.
• Reset the number of CT
power wire loops.
• Check the wiring.
Handling Precautions
If ROM version 1 of the instrument information bank (Id02) is prior to
2.04, CT input failure (AL11) is not displayed.