Manual
5-73
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
5 - 14 Console Display and Key Operation
It is possible to make the setting so that the console display and key operation are customized.
■ Key operation type
Two kinds of general key operation flows are provided, standard key operation
type and special key operation type. A desired key operation type can be selected.
(For details about two kinds of key operation types,
refer to 2-2, Key Operation (on page 2-2).)
■ [mode] key function
The selection operation when the [mode] key is kept pressed for 1 sec. or longer
in the operation display mode can be set.
Handling Precautions
•When [CtrL: Control method] is set at “0” (ON/OFF control), the
AUTO/MANUAL selection becomes invalid.
•When [CtrL: Control method] is set at “0” (ON/OFF control) or if the
PV high limit/low limit alarm occurs, the AT stop/start selection
becomes invalid.
• When [C30: LSP system group] is set at “1”, the LSP group selection
becomes invalid.
Item (Setting display/bank) Display Contents Initial value User level
Key operation type
(Setup setting/Setup bank)
0: Standard type
1: Special type
0
High function
Item (Setting display/bank) Display Contents Initial value User level
[mode] key function
(Setup setting/Setup bank)
0: Invalid
1: AUTO/MANUAL selection
2: RUN/READY selection
3: AT Stop/Start
4: LSP group selection
5: Release all DO latches
6: Invalid
7: Communication DI1 selection
8: Invalid
0
Simple,
Standard,