Manual

5-73
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
5 - 14 Console Display and Key Operation
It is possible to make the setting so that the console display and key operation are customized.
Key operation type
Two kinds of general key operation flows are provided, standard key operation
type and special key operation type. A desired key operation type can be selected.
(For details about two kinds of key operation types,
refer to 2-2, Key Operation (on page 2-2).)
[mode] key function
The selection operation when the [mode] key is kept pressed for 1 sec. or longer
in the operation display mode can be set.
Handling Precautions
•When [CtrL: Control method] is set at “0” (ON/OFF control), the
AUTO/MANUAL selection becomes invalid.
•When [CtrL: Control method] is set at “0” (ON/OFF control) or if the
PV high limit/low limit alarm occurs, the AT stop/start selection
becomes invalid.
When [C30: LSP system group] is set at “1”, the LSP group selection
becomes invalid.
Item (Setting display/bank) Display Contents Initial value User level
Key operation type
(Setup setting/Setup bank)
0: Standard type
1: Special type
0
High function
Item (Setting display/bank) Display Contents Initial value User level
[mode] key function
(Setup setting/Setup bank)
0: Invalid
1: AUTO/MANUAL selection
2: RUN/READY selection
3: AT Stop/Start
4: LSP group selection
5: Release all DO latches
6: Invalid
7: Communication DI1 selection
8: Invalid
0
Simple,
Standard,