Manual
◆ Setting example
• Event
Note. The internal event No. is indicated at the mark of "x" shown in the Display
column.
• DI Assignment
Note. The internal DI No. is indicated at the mark of "x" shown in the Display
column.
5-64
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Event Display Internal Event 1 Internal Event 2
Operation type Ex.C1 9: Deviation high/low limit 32: Timer (Status)
(Final SP reference)
Direct/reverse Ex.C2 1: Reversed. ----
Standby Ex.C2 0: No standby ----
EVENT state at READY Ex.C2 1: EVENT state at READY 0: EVENT state at READY
is forcibly turned OFF. is continued.
Alarm OR Ex.C3 0: None 0: None
Special OFF setup Ex.C3 0: As usual. ----
Delay time unit Ex.C3 0: 0.1s 0: 0.1s
Event main setting Ex 3 ----
(low limit)
Event sub setting Ex.SB 3 ----
(high limit)
Hysteresis Ex.HY 9999 ----
ON delay Ex.ON 2 15
OFF delay Ex.OF 0 0
DI Assignment Display Internal Contact 1 Internal Contact 2
Operation type DIx.1 7: RUN/READY 17: Timer stop/start
Input bit function DIx.2 1: Function 1 (A and B) or 1: Function 1 (A and B) or
(C and D) (C and D)
Input assign A DIx.3 18: COM DI 1 10: Internal Event 1
(Setting = 9: Deviation
high/low limit (Final SP
reference)
Input assign B DIx.4 11: Internal Event 2 26: During SP ramp
(Setting = 32: Timer
(Status))
Input assign C DIx.5 0: Normally opened. 18: COM DI 1
(Normally Off = 0)
Input assign D DIx.6 0: Normally opened. 11: Internal Event 2
(Normally Off = 0) (Setting = 32:
Timer (Status))
Polarity A DIx.7 0: Direct 0: Direct
Polarity B DIx.7 1: Reverse 1: Reverse
Polarity C DIx.7 0: Direct 0: Direct
Polarity D DIx.7 0: Direct 0: Direct
Polarity DIx.8 1: Reverse 0: Direct
Event channel def.
DIx.9 ---- 2