This section describes examples of applications using the assign functions of this unit.
■ Examples of applications using assign functions
The following shows setting examples with the Smart Loader Package SLP-C35.
To use assign functions, it is absolutely necessary to set the user level to “High
function configuration”.
● Example 1 Logical OR of the heater burnout and PV high limit alarm is output.
Conditions: PV high limit is set to Internal Event 1.
Heater burnout is set to Internal Event 2.
Logical OR of the above events is output to the EV1 relay.
(1) Select [Standard] → [Event] and set [Internal Event 1] to [1: PV high limit].
(2) Similarly, set [Internal Event 2] to [16: Heater 1 break/Heater over
current].
(3) Select [Option] → [DO Assignment] and right-click on the operation type of
[Event output 1] to select [Input/Output port setup].