Owner manual
2828
Visit our Web Site www.n-c.com
IntellIsys AdAptIve pressure Controllers
APC-OP-LIT 1/12
9.6 - Connection Object
Class ID 5 hex
Instance ID 1, 2 (1=EC, 2=IO)
• Attribute E &10: Setting of this
attribute is allowed only when in
configure I/O state.
• Attempt to set unsupported
EPATH returns an “invalid
attribute value” error.
• The current assembly path is
stored in the device’s NVRAM
and restored on power up.
• Watch dog timeout action:
0= transition to timeout,
1= auto delete.
• Attribute 7 and 8: report 12 for
explicit connection or the actual
static assembly length in IO.
9.5 - I/O Assembly Instances
TABLE 9.5.1 - INPUT ASSEMBLY INSTANCES
INSTANCEHEX BYTE VARIABLES EPATH (HEX)
2
0
1-2
Exception status
Process variable
20 04 24 02 30 03
4
0
1-2
3-4
Exception status
Process variable
Control setpoint
20 04 24 04 30 03
5 (factory
setting)
0
1-2
3-4
5-6
Exception status
Process variable
Control setpoint
Valve position
20 04 24 05 30 03
9.4 - Assembly Object
Class ID 4 hex
Instance ID (see static assembly Table 9.5.1 and 9.5.2)
Get or set service selectively supported as a function of
the selected instance in the connection object.
9.7 - Discrete Input Point Object
Class ID 8 hex
Instance ID 1
1 = closed
0 = not closed
Instance ID 2
1 = open
0 = not open
TABLE 9.7.1 – DISCRETE INPUT POINT OBJECT ATTRIBUTE; INSTANCE ID 1
ATTRIBUTE IDHEX ACCESS CODE NAME FORMAT VALUE
3
0E (get) Close limit switch BOOL 0-1 mirror close LED
TABLE 9.7.2 - DISCRETE INPUT POINT OBJECT ATTRIBUTE; INSTANCE ID 2
ATTRIBUTEIDHEX ACCESS CODE NAME FORMAT VALUE
3
0E (get) Open limit switch BOOL 0-1 mirror open LED
TABLE 9.6.1 – CONNECTION OBJECT ATTRIBUTES
ATTRIBUTE
ID
HEX
ACCESS CODE
NAME
FORMAT
VALUE
1 0E (get)
State
UINT
0-5, 0=no cxn, 3=cxnted
2 0E (get)
Instance type
UINT
0=explicit, 1=IO
3 0E (get)
Transport class trigger
BYTE
80,82,83
4 0E (get)
Produced connection ID
UINT
FBh 05h (EC), FFh 03h (IO)
5 0E (get)
Consumed connection ID
UINT
FCh 05h (EC), FDh 05h (IO)
6 0E (get)
Initial com. char.
BYTE
21 for EC, 01 for IO
7 0E (get)
Produced connection size
UINT
12h (EC), 7h (IO)
8 0E (get)
Consumed connection size
UINT
12h (EC), 3h (IO)
9 0E (get) 10 (set)
Expected packet rate
UINT
Connection timing
C 0E (get)
Watchdog time out action
UINT
1 for EC, 0 for IO
D 0E (get)
Produced connection length
UINT
0 in EC, 6 in IO
E 0E (get) 10 (set)
Produced connection path
EPATH
IO input assembly path
F 0E (get)
Consumed connection length
UINT
0 in EC, 6 in IO
10 0E (get) 10 (set)
Consumed connection path
EPATH
IO output assembly path
11 0E (get)
Production inhibit time
UINT
00
TABLE 9.5.2 - OUTPUT ASSEMBLY INSTANCES
INSTANCEHEX BYTE VARIABLES EPATH (HEX)
7 (factory setting) 0-1
2
Control setpoint
Control instance
20 04 24 07 30 03
TABLE 9.4.1 – ASSEMBLY OBJECT ATTRIBUTES
ATTRIBUTE ID HEX ACCESS CODE NAME FORMAT VALUE
3
0E (get) 10 (set) Data ARRAY Static assembly
The control instance: indicates the
significance of the control setpoint,
1 = pressure control high guage
2 = position control.
3 = pressure control low gauge