Owner manual
13
Call toll free 800-824-4166 or 530-842-4457 • FAX 530-842-9130
IntellIsys AdAptIve pressure Controllers
APC-OP-LIT 1/12
TABLE 3.7.1 –
(J1) “IQD” DEVICENET
NETWORK CONNECTOR
PIN FUNCTION
1
Drain
2
Power In +
3
Power In -
4
CAN H
5
CAN L
1
4
3
2
5
AUXILIARY
GAUGE
TM
Valve Open/Close
membrane switches
Indicating LEDs
3.7 - DC Powered IQD Controlled Valve with Serial and DeviceNet I/O Interface
Refer to the following diagram and tables when connecting to an IQD controller including models TBV-IQD, TSS-IQD and TPV-IQD.
TABLE 3.7.3 – (J3) “IQD”
GAUGE CONNECTOR,
DB-9 RECEPTACLE
PIN # FUNCTION
1
Signal input from gauge 1
2
+15 V supply to gauge
3
-15 V supply to gauge
4
Not used
5
Signal input from gauge 2
6
Signal common from gauge 2
7
Not used
8
Signal common from gauge 1
9
Power supply common
TABLE 3.7.2 – (J2) “IQD”
AUXILIARY CONNECTOR,
DB-15 RECEPTACLE
PIN FUNCTION
1
Not used
2
RS-232 TX (data from IQ to
host)/485 (A)
3
RS-232 RX (data from host to
IQ)/485 (B)
4
Digital GND
5
Power RTN
6
Not used
7
Power +24V in
8
Not used
9
Analog CDG1 Out
10
Analog Valve Out
11
Analog GND
12
TTL Out Common
13
\Valve Open Out\
14
\Valve Closed Out\
15
Chassis GND