Note
In general, the fuses for cable protection must be rated according to the national
electrical safety regulations.
For information on the pin configurations for the different BTS power supply
connector types, refer to Nokia MetroSite EDGE Base Station: Product
Description.
3.7 Painting the BTS cover
If desired, the BTS cover can be painted to blend into the surrounding
environment, although some dark colours with high absorptivity may be
restricted because of heat retention.
For painting the cover, Nokia recommends a primer-topcoat combination of
Beckers TD 130 primer and Beckers TH 141 surface paint. Other paints suitable
for polycarbonate surfaces may also be used.
Table 6. Connectors, cables and recommended fuses
Power
supply
type
Connector
type at the
end of cable
Cable
Recommended
fuse for cable
protection
AC supply
230 V
IEC 320
(female)
Multicore cable 3 x 0.75 to
1.5 mm
2
(18
1
/
2
to 15
1
/
2
AWG)
10A for 1.5 mm
2
(15
1
/
2
AWG)
6A for 0.75 mm
2
(18
1
/
2
AWG)
AC supply
110 V
IEC 320
(female) with
notch
Multicore cable 3 x 1.5
mm
2
(15
1
/
2
AWG)
10 A
DC supply -
48 V
Anderson
Power Pole
Multicore cable 3 x 2.5
mm
2
or 3 single wires 2.5
to 4.0 mm
2
(13 to 11
AWG)
No recommendation,
refer to local
regulations
DC supply
+24 V
Anderson
Power Pole
Multicore cable 3 x 2.5
mm
2
or 3 single wires 2.5
to 4.0 mm
2
(13 to 11
AWG)
No recommendation,
refer to local
regulations