Outdoor (cabinet - mount) GAP installation Chapter 5: Outdoor GAP Hardw are Installation
Outdoor (cabinet - mount) GAP installation
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
■
■
This section provides general information to install the Ground - based Access P oint (GAP) in an
outdoor environment. Each customer installation will vary . All outdoor GAP installations require
the use of a 5 - ft by 7 - ft concrete slab capable of supporting one ton (2000 lbs or 900 kg). Side
- by - side cabinets will require the use of two 5 - ft by 7 - ft concrete slabs.
GAP cabinets
The GAP cabinet comes pre -loaded with hardware cages. Cards, modules, and batteries are
installed separately in the GAP cages after the main mounting to a concrete or other support (re
- enforced floor) surface. Installation of the cards, modules, and batteries are customer site
dependent, and are not specifically covered in this manual.
The GAP cabinets are hea vy . The use of a cr ane and / or hoisting system that is r ated
to handle at least two tons (4000 lbs or 1800 kg) is recommended. A four -point
hoisting cable with appropriate hooks or car abiners should be used to unload the GAP
cabinet from the shipping pallet to the area of nal installation.