Installation Instructions

Adding a second/third PSM (–48 V or 220 V AC only) Chapter 3: Low -to -Mid Capacit y Fr ame Expansion Procedures
Procedure
Procedure 3 -6 contains the steps for adding a second/third PSM to the PSM shelf .
Procedure 3 -6 Adding a 2nd/3rd PSM to the PSM shelf
1
If a PSM is to be installed in PSM shelf slot 3, use a T25 TORX bit and driver
to completely loosen the captive retaining thumbscrew on the filler plate that
covers slot 3 of the PSM shelf . Remove the filler plate.
2
PSM weighs appro ximately 5 kg. Be careful when handling the PSM
to prev ent damage to the equipment and personal injury .
Install the appropriate PSM into PSM shelf slot 2 and 3 as follows:
1. Grasp the handle on the front panel of the PSM with one hand while
carefully supporting the bottom of the module with the other hand.
2. Properly orient the PSM and insert it into the slot.
3. Slowly slide the module into the shelf until the rear connectors are
fully seated. Make sure that the PSM is fully engaged with the shelf
backplane slot connectors.
3
Using a T25 TORX bit and torque driver , tighten the captive retaining
thumbscrew to 2.37 N-m (21 in-lb).
3 -20 68P09283A62 -2