User's Manual Part 1

Outdoor Enclosure Equipment Identification – continued
DRAFT
1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU
Jun 2004
1-30
Figure 1-10: Power Distribution Assembly
ti–cdma–wp–00350–v01–ildoc–ah
Power Distribution Enclosure
The following are brief descriptions of the components of the PDE.
PDE
The Power Distribution Enclosure converts AC voltage to DC voltage
for use by the TME and Compact Combined Linear Power Amplifier
(cCLPA). Battery backup is routed through the PDE. See Figure 1-11.
S AC Load Center (ACLC) – Where the AC voltage is connected to the
PDE. Also contains AC surge protection.
S Power Supply Module (PSM) – Converts the 220–240 VAC to +27 V
DC for use by the TME, BTS, and cCLPA.
S Power Management Alarm Card (PMAC) – Monitors alarms for PDE
and battery backup.
S Circuit Breakers (CB) – Provides DC surge and DC short circuit
protection.
S Punch Block (PB) – Distribution point for incoming and outgoing
data signal lines.
S Multiple ground connections at the reaar of the PDE
S Antenna surge arrestors slots
HX
The Heat Exchanger attaches to the PDE and provides temperature
regulation.
1