User Manual
Pinging the Processor – continued
3-32 1X SC4812T–MC BTS Optimization/ATP 5/21/04
DRAFT
Always wear an approved anti–static wrist strap while
handling any circuit card/module to prevent damage by
ESD.
CAUTION
The Ethernet LAN A and B cables must be installed on
each frame/enclosure before performing this test. All other
processor board LAN connections are made via the
backplanes.
NOTE
Table 3-11: Pinging the Processors
n Step Action
1 If it has not already been done, connect the LMF to the BTS (see Table 3-5 on page
3-15).
2 From the Windows desktop, click the Start button and select Run.
3 In the Open box, type ping and the <MGLI IP address> (for example, ping
128.0.0.2).
NOTE
128.0.0.2 is the default IP address for MGLI–1 in field BTS units. 128.0.0.1 is the
default IP address for MGLI–2.
4 Click on the OK button.
5 If the connection is successful, text similar to the following is displayed:
Reply from 128 128.0.0.2: bytes=32 time=3ms TTL=255
If there is no response the following is displayed:
Request timed out
If the MGLI fails to respond, reset and perform the ping process again. If the MGLI
still fails to respond, typical problems are shorted BNC–to–inter-frame cabling, open
cables, crossed A and B link cables, missing 50–Ohm terminators, or the MGLI itself.
3