BTS Redundancy/Alarm Testing – continued
3-94 1X SC4812T–MC BTS Optimization/ATP 5/21/04
DRAFT
Figure 3-26: C–CCP Shelf
19 mm Filler Panel
PS–3
AMR–1
CSM–1
CSM–2
38 mm Filler Panel
AMR–2
GLI–1GLI–2
MCC–6
BBX–1
BBX–2
BBX–3
BBX–4
BBX–5
BBX–6
BBX–RSwitch
MPC/EMPC–1MPC/EMPC–2
MCIO
BBX–7
BBX–8
BBX–9
BBX–10
BBX–11
BBX–12
MCC–5
MCC–4
MCC–3
MCC–2
MCC–1
MCC–12
MCC–11
MCC–10
MCC–9
MCC–8
MCC–7
PS–2
PS–1
CCD–2 CCD–1
NOTE: MCCs may be
MCC24Es, MCC8Es, or
MCC–1Xs. GLIs may be
GLI2s or GLI3s.
HSO/LFR
ti-CDMA-WP-00037-v01-ildoc-ftw
Miscellaneous
Alarm/Redundancy Tests
Follow steps in Table 3-42 to verify that alarms reported by the master
GLI are displayed via the alarm monitor if a BTS frame module failure
occurs.
Table 3-42: Miscellaneous Alarm Tests
Step Action
1 Select Util>Alarm Monitor to display the alarm monitor window.
2 Perform the following to verify fan module alarms:
• Unseat a fan module (see Figure 3-27).
• Observe an alarm message was reported via the MGLI (as displayed on the alarm monitor).
• Replace fan module and verify the alarm monitor reports that the alarm clears.
• Repeat for all other fan modules in the BTS frame.
NOTE
Follow Step 3 for Starter Frames and Step 4 for Expansion Frames.
3 Starter Frames Only: Perform the following to verify MPC module alarms.
• Unseat MPC modules (see Figure 3-26) one at a time.
• Observe that an alarm message was reported via the MGLI as displayed on the alarm monitor.
• Replace the MPC modules and verify the alarm monitor reports the alarm clears.
3