User's Manual

Power, Ground, and Battery Cabling for Sites Equipped with
CustomerSupplied Site I/O Interface
continued
DRAFT
SC300 1X BTS Hardware Installation, ATP, and FRU Procedures
JAN 2002
4-12
Table 4-13: AC Input Cable Information
Connector Wire Color Description
A Black Line
B Green Ground
C White Neutral
DC Input Cable Information
The information for the DC input cable(s) (Cable U) is given in
Figure 4-6.
Figure 4-6: DC Input Cable Connector Information
A
B
C
D
SOCKET POSITION ON
CABLE CONNECTOR SHOWN
Table 4-14: DC Input Cable Information
Connector Wire
Color
Description Comments
A Yellow Switch A No connection
B Red Positive Connect to positive
terminal of supply.
C Blue Switch B Connect to negative
terminal of supply.
D Black Negative Connect to negative
terminal of supply.
Procedures to Install Earth
Ground, AC/DC Power, and
Battery Cabling
The system configuration determines which power cables are installed.
The ground cable is always installed. Perform the appropriate
procedures from the following tables based on the system configuration.
4