Service Manual
GSM-205-423
Installing and connecting power and earth cabling
31st Oct 01
Installation & Configuration: Horizon
macro
indoor
68P02902W08-B
CONTROLLED INTRODUCTION
Inst. 2–57
– 48/60 V dc
connection
procedure
To connect dc power cables to a –48/60 V dc cabinet:
WARNING
Each cabinet must be earthed separately and not daisy
chained together.
1. Route the earth wire from the building master earth and connect to the
earth stud on top of the cabinet. Tighten to the correct torque (see
Installation & Configuration: GSM-205-423
Site requirements and
considerations).
WARNING
Do not make input power connections at the main power
source at this time. Connecting input power is the final
installation procedure in this chapter.
2. Thread the cone-shaped plastic covers onto the cables before connection.
3. Connect the black 0 volt (+ve) dc power cable to the cabinet dc power
connector assembly 0 V terminal, and route to the main dc power source
4. Connect the blue –48/60 volt (–ve) dc power cable to the cabinet dc power
connector assembly V IN terminal, and route to the main dc power source.
5. Tighten the dc power terminal connections (nuts on studs with star
washers) to correct torque as in step 1.
The –48/60 volt dc power cable connection procedure is now complete.