Service Manual

GSM-204-423
Site requirements and considerations
31st Oct 01
Installation & Configuration: Horizon
macro
outdoor
68P02902W03-A
CONTROLLED INTRODUCTION
Inst. 2–3
Power
requirements
The power requirements of cabinets depends on the configuration.
Power consumption (dc and ac)
Table 2-5 lists typical and maximum power consumption values.
Table 2-5 Power consumption of full cabinet, including digital redundancy
and external battery charging
Typical measured consumption Maximum power consumption
2200 W 5600 W
NOTE Maximum power consumption figures are theoretical
values derived under extreme conditions and are affected
by variables such as temperature, component tolerances,
transmission power and supply voltage. Although these
figures must be considered when planning site power
requirements, typical measured consumption values will
be lower.
Cabinet input power supply requirements
WARNING All cabinets and supply cables must be protected by an
upstream fuse or circuit breaker.
Table 2-6 lists the power supply requirements for the different power supply
options.
Table 2-6 Main outdoor cabinet power requirements
Nominal voltage Supply voltage
and frequency
range
Current supply
maximum
110 V ac single phase 88 to 134 V ac
at 45 to 66 Hz
54.4 A
(at nominal voltage)
230 V ac single phase 176 to 265 V ac
at 45 to 66 Hz
26.1 A
(at nominal voltage)
230 V ac three phase
and neutral (star)
176 to 265 V ac
at 45 to 66 Hz
26.1 A
(at nominal voltage)
230 V ac three phase
without neutral (delta)
176 to 265 V ac
at 45 to 66 Hz
26.1 A
(at nominal voltage)