Service Manual

GSM-204-323
Control and alarm board (CAB)
31st Oct 01
Tech. 4–14
Technical Description: Horizon
macro
outdoor
CONTROLLED INTRODUCTION
68P02902W02-A
Control and alarm board (CAB)
Introduction to
the CAB
The CAB is located in the outdoor PSU between the dc circuit breaker panel
and the number 2 ac distribution box. It provides the following functions:
Control of TOPSM output voltage (voltage trim).
TOPSM disable relay control.
Control of battery and communications contactors:
During cabinet power up.
During low voltage disconnect (LVD).
Monitoring of battery voltage and temperature.
Monitoring of TOPSM input and output failure signals.
Monitoring of non EMC enclosure temperature.
Monitoring of alarms from the cabinet, the TMS, and the auxiliary
equipment housing.
Performing a battery charge capacity test on the internal batteries.
The CAB sources dc power from all of the following:
The distributed dc regulated output of the TOPSMs.
The TOPSM auxiliary output.
The communications equipment side of the outdoor PSU communications
contactor.