Service Manual

GSM-204-323
AC power distribution
31st Oct 01
Tech. 4–6
Technical Description: Horizon
macro
outdoor
CONTROLLED INTRODUCTION
68P02902W02-A
AC distribution
description
There are two ac distribution boxes and an ac power outlet socket associated
with the Horizon
macro
outdoor PSU.
Number 1 ac distribution box
The number 1 ac distribution box (see Figure 4-5) is located in the top panel of
the cabinet. It contains circuit protective devices and a terminal block, and
provides:
The termination point for the incoming mains supply.
A four pole 32 A main circuit breaker (also used as a switched disconnect
for external ac power supplies).
A double pole 6 amp (30 mA) residual current breaker with overcurrent
protection (RCBO) to supply the ac power outlet socket.
The means of configuring the BTS to accept the following incoming mains
supply voltages:
230 V ac 50 Hz single phase and neutral.
230 V ac 50 Hz three phase and neutral (star configuration).
230 V ac 50 Hz three phase (delta configuration).
110 V ac 60 Hz single phase and neutral.
NOTE
When the Horizon
macro
is supplied by 110 V single
phase, the 4 pole main circuit breaker is configured as two
parallel pairs – one pair breaking the live phase and one
pair breaking the neutral. This provides circuit protection at
a total of 64 amps.
MAINS DISCONNECT
4 POLE 32 A TYPE C
AC SOCKET
6 A 30mA
1 3 5 7 9 11
2 4 6 8 10 12
Figure 4-5 The number 1 ac distribution box