User's Manual Part 3

BTS Redundancy/Alarm Testing
Mar 2001
3-85
68P09253A61
SCt4812T CDMA BTS Optimization/ATP
DRAFT
Objective
This section tests the redundancy options that could be included in the
cell site. These tests verify, under a fault condition, that all modules
equipped with redundancy switch operations to their redundant partner
and resume operation. An example would be to pull the currently active
CSM and verify the standby CSM takes over distribution of the CDMA
reference signal.
Redundancy covers many BTS modules. Confirm the redundant options
included in the BTS, and proceed as required. If the BTS has only basic
power supply redundancy, the tests and procedures detailed in the
following tables should be bypassed.
Table 3-48. Miscellaneous Alarm Tests (BTS Frame)
Table 3-49. BBX Redundancy Tests (BTS Frame)
Table 3-50. CSM, GPS, & LFR/HSO Redundancy Alarm Tests
Table 3-51. LPA Redundancy Test
Table 3-52. MGLI/GLI Redundancy Test
During redundancy verification of the test, alarms reported by the master
GLI (displayed via the alarm monitor) will also be verified/noted.
Test Equipment
The following pieces of test equipment are required to perform this test:
LMF
Communications Test Set
Redundancy/Alarm Test
Perform each of the following tests to verify BTS redundancy and to
confirm all alarms are received and reported by the BTS equipment. The
procedures should be performed on the following modules/boards:
Power supply/converter modules in all frames
Distribution shelf modules in the BTS frame
CCCP shelf modules in the BTS frame (except MCCs)
LPA modules in the BTS frame
AMR Customer defined input/output tests
3